InteliLite4 AMF20 Global Guide
123
Alarms / Protection name
Speed
Engine protections
User Protections
InteliLite 4 allows users to configure their own protections to any analog input or binary input/output. Only one
protection of 1st level and/or one protection of 2nd level can be configured on logical binary input/output.
More than one protection can be configured on analog input. Max simultaneous number of configured user
protections is 64.
Source upon which the protection is configured can be selected. It can be any analog value or binary state.
Analog values
Binary states
Analog inputs
Controller, Modules
Values
ECU, Generator, Mains, others
Statistics
Binary inputs
Controller, Modules, ECU
Binary outputs
PLC
Protection states
LBOs
Source
Type
Name of activation
Description
Analog
Over Limit
Protection is activated if value is over limit.
Over Limit + Fls
Protection is activated if value is over limit or in a fault state.
Under Limit
Protection is activated if value is under limit.
Under Limit + Fls
Protection is activated if value is under limit or in a fault state.
Fls only
Protection is activated if value is in a fault state.
Binary
True
Protection is activated if value is Logical 1.
TrueOrFls
Protection is activated if value is Logical 1 or in a fault state.
False
Protection is activated if value is Logical 0.
FalseOrFls
Protection is activated if value is Logical 0 or in a fault state.
Protection activation