InteliLite4 AMF20 Global Guide
560
Note:
The MCB control is not affected by this alarm.
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Emergency Stop
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Alarm is activated when dedicated E-Stop input is activated. The Gen-set shuts
down in the moment the input is activated and starting is blocked until the input is
deactivated and fault reset is pressed.
Sd E-Stop
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Wrn Charging Alternator Fail
Alarm evaluated
Engine running only
Related applications
AMF, MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than 80%
of the controller supply voltage. This
alarm works similar to the red “battery” alarm indicator on a vehicle dashboard.
The setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Sd Charging Alternator Fail
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Overspeed
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit.
The behavior of the overspeed alarm is adjusted by the following setpoints:
adjust the overspeed limit
Sd Overspeed
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Underspeed
Alarm evaluated
Engine running only
Related applications
AMF, MRS
Description
This alarm will be issued when the Gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint
.
The underspeed alarm starts to be evaluated after successful Gen-set start and
is being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed