148
Range [units]
0 .. 200 [%]
Related FW
3.0
Description
This setpoint adjusts threshold for busL current asymmetry (unbalance). The
current unbalance is calculated as a maximum difference between phase
currents. This condition is evaluated with delay adjusted by
12.2.6.18
Setpoint: BusL Iunb del
Group
BusL protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
Delay for BusL current asymmetry (unbalance). This protection treshold is
adjusted by
12.2.7 Group: BusR protect
12.2.7.1
Setpoint: BusRVolt prot
Group
BusR protect
Range [units]
ENABLED, DISABLED [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint enables or disables BusR voltage protection. For more
information on this protection see setpoints
N
OTE
:
If both voltage and frequency protections (see also setpoint
are disabled there is no way for the controller to decide whether the BusR is
healthy or not. In this case BusR is considered healthy if there is any voltage.
12.2.7.2
Setpoint: BusRight >V
Group
BusR protect
Range [units]