Unitary Products Group
21
345095-CTG-B-0907
Multipliers for determining the performance with other indoor section.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
HEATING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
HC8B024F1
INDOOR COIL MODEL NO.
FC/MC/PC48D + MV12D
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
750
850
950
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
31.6 1.7 5.4 32.0 1.7 5.6 32.4 1.6 5.9
70
30.9 1.9 4.8 31.4 1.8 5.0 31.9 1.8 5.3
80
30.2 2.0 4.4 30.7 2.0 4.6 31.3 1.9 4.8
47
60
26.8 1.6 4.8 27.0 1.6 5.0 27.2 1.5 5.2
70
26.4 1.8 4.3 26.6 1.7 4.5 26.8 1.7 4.7
80
25.9 1.9 3.9 26.1 1.9 4.1 26.3 1.8 4.2
40
60
24.4 1.6 4.5 24.5 1.5 4.7 24.6 1.5 4.9
70
23.9 1.7 4.1 24.1 1.7 4.2 24.3 1.6 4.4
80
23.5 1.9 3.7 23.7 1.8 3.8 23.9 1.8 3.9
30
60
20.7 1.5 4.1 20.9 1.5 4.2 21.0 1.4 4.3
70
20.5 1.6 3.7 20.7 1.6 3.8 20.8 1.6 3.9
80
20.4 1.8 3.3 20.5 1.7 3.4 20.6 1.7 3.5
17
60
16.6 1.4 3.5 16.7 1.4 3.6 16.8 1.3 3.7
70
16.6 1.5 3.2 16.6 1.5 3.3 16.7 1.5 3.3
80
16.5 1.7 2.9 16.6 1.6 3.0 16.6 1.6 3.0
10
60
14.8 1.3 3.2 14.8 1.3 3.3 14.8 1.3 3.4
70
14.7 1.5 2.9 14.7 1.5 3.0 14.8 1.4 3.0
80
14.6 1.6 2.7 14.7 1.6 2.7 14.8 1.6 2.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
AV36
-
1.00 0.99 1.01
MV12B
FC/MC43B
1.00 1.00 1.00
MV12D
FC/MC60D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC9(C,V)*B12
FC/MC/PC43B
1.00 0.98 1.02