16
Unitary Products Group
345095-CTG-B-0907
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
HC8B048F1
INDOOR COIL MODEL NO.
FC/MC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1000
1050
1100
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
33.8 35.9 35.8 39.4 43.5 34.4 36.3 36.2 39.9 43.9 35.0 36.8 36.6 40.4 44.4
S.C.
33.8 31.5 26.6 26.7 22.2 34.4 32.4 27.2 27.4 22.5 35.0 33.3 27.8 28.0 22.8
K.W.
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
75
T.C.
32.6 34.2 34.1 37.7 41.5 33.2 34.6 34.5 38.1 42.0 33.7 35.0 34.8 38.5 42.4
S.C.
32.6 30.8 25.9 26.0 21.3 33.2 31.7 26.5 26.6 21.6 33.7 32.6 27.1 27.3 21.9
K.W.
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
85
T.C.
31.4 32.5 32.5 36.0 39.6 31.9 32.9 32.8 36.3 40.0 32.5 33.2 33.1 36.7 40.4
S.C.
31.4 30.1 25.2 25.3 20.4 31.9 31.0 25.8 25.9 20.7 32.5 31.9 26.4 26.5 21.1
K.W.
2.1 2.1 2.1 2.0 2.0 2.1 2.1 2.1 2.0 2.0 2.1 2.1 2.1 2.0 2.0
95
T.C.
30.2 30.8 30.8 34.2 37.6 30.7 31.1 31.1 34.6 38.0 31.2 31.5 31.4 34.9 38.4
S.C.
30.2 29.5 24.5 24.5 19.4 30.7 30.3 25.1 25.1 19.8 31.2 31.2 25.7 25.7 20.2
K.W.
2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
105
T.C.
28.3 28.7 28.2 31.6 34.9 28.7 29.0 28.4 31.8 35.2 29.2 29.4 28.7 32.1 35.5
S.C.
28.3 27.8 23.3 23.5 18.4 28.7 28.5 24.0 24.1 18.7 29.2 29.2 24.6 24.7 19.1
K.W.
2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
115
T.C.
26.4 26.7 25.6 29.0 32.2 26.9 27.0 25.9 29.2 32.4 27.3 27.4 26.1 29.4 32.7
S.C.
26.4 26.2 22.3 22.4 17.3 26.9 26.7 22.9 23.1 17.7 27.3 27.3 23.5 23.7 18.0
K.W.
3.1 3.1 3.1 3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.0 3.1 3.0 3.0
125
T.C.
24.6 24.6 23.0 26.5 29.5 25.0 25.0 23.3 26.6 29.7 25.3 25.3 23.5 26.7 29.8
S.C.
24.6 24.6 21.2 21.4 16.2 25.0 25.0 21.8 22.0 16.6 25.3 25.3 22.4 22.6 17.0
K.W.
3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AV/SV48
-
1.01 1.02 0.99
AV/SV60
-
0.99 1.01 0.97
MV16C
FC/MC48C
1.01 1.02 0.99
MV20D
FC/MC48D
0.99 0.97 0.96
MV20D
FC/MC60D
0.98 0.97 0.95
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
(F,L)C8(C,V)*C16
FC/MC/PC48C
0.98 0.91 0.96
(F,L)C8(C,V)*C20
FC/MC/PC48C
0.98 0.97 0.96
FC9(C,V)*C16
FC/MC/PC48C
1.01 1.01 1.00
FC9(C,V)*C20
FC/MC/PC48C
0.98 0.95 0.95
FC9(C,V)*D20
FC/MC/PC48D
0.98 0.95 0.96
(F,L)C8(C,V)*C16
FC/PC60C
0.95 0.91 0.96
(F,L)C8(C,V)*C20
FC/PC60C
0.98 0.98 0.96
FC9(C,V)*C16
FC/PC60C
0.99 1.01 0.99
FC9(C,V)*C20
FC/PC60C
0.98 0.97 0.96
FC9(C,V)*D20
FC/MC/PC60D
0.98 0.95 0.96
(F,L)C8(C,V)*C20
FC/MC62D
0.99 0.98 0.98
FC9(C,V)*C20
FC/MC62D
0.98 0.98 0.96
FC9(C,V)*D20
FC/MC62D
0.98 0.96 0.96