background image

DeviceNet

®

 Interface Module Installation & Reference

 

 

 

 

 

Overview 

The Cognex In-Sight

®

 5000 series and In-Sight 3400 vision sensors can communicate with a PLC using 

discrete I/O, DeviceNet, or both. This document describes how to configure communications between the 
In-Sight sensor and a PLC using the optional DeviceNet Interface Module (referred to as “the Interface 
Module”), and includes the following topics: 

Preparing for Installation ....................................................................................p. 1

 

Connecting the Interface Module to a DeviceNet Network ................................p. 2

 

Connecting the Interface Module to In-Sight .....................................................p. 4

 

Communicating With In-Sight via DeviceNet .....................................................p. 6

 

Troubleshooting ...............................................................................................p. 11

 

Specifications ...................................................................................................p. 12

 

 

The DeviceNet interface module is a serial-to-DeviceNet gateway. The In-Sight sensor communicates to 
the Interface Module through a serial port, the Interface Module buffers the serial data and sends it 
through DeviceNet to (or from) a DeviceNet scanner attached to a PLC. 

To set up this connection, configure two communications channels: one from the In-Sight sensor to the 
DeviceNet Interface Module, and the other from the DeviceNet Scanner/PLC to the Interface Module. 

Preparing for Installation 

The DeviceNet Interface Module kit (Cognex P/N CIO-2550-00) includes the following components: 

 

DeviceNet Interface Module (P/N 147-0001) 

 

DeviceNet Interface Module diskette (P/N 206-6193), containing a copy of the EDS file for use 
with the DeviceNet Interface Module and an In-Sight icon. 

To complete the installation, you will also need the following: 

 

A configured DeviceNet network that includes a scanner attached to a PLC. 

 

An In-Sight 5000 series vision sensor. 

 

An RS232 serial cable that supports RTS/CTS hardware handshaking. 

Finally, you will need the software installed on a PC to configure and run the PLC. To illustrate the 
instructions in this manual, the following was used:

 

 Allen-Bradley™ 

PLC 

 

RSNetworx for DeviceNet

  

 RSLinx

 

 RSLogix 

500

  

Summary of Contents for CIO-2550-00

Page 1: ...it through DeviceNet to or from a DeviceNet scanner attached to a PLC To set up this connection configure two communications channels one from the In Sight sensor to the DeviceNet Interface Module and...

Page 2: ...S file contained on the DeviceNet Interface Module diskette supplied using the EDS Wizard 2 On the Interface Module set the two rotary MACID switches to the unused MACID you want to assign to the modu...

Page 3: ...stance 1 Parameter 8 1 byte which defines the length of the receive byte array c Parameter 69 Data Size Instance 1 Parameter 8 1 byte which defines the length of the transmit byte array d Parameter 49...

Page 4: ...nd data this changes from a value of 0 to a value of 1 triggering the PLC to send the data to the Interface Module the second byte is a sync byte and the third is the size of data being sent user ente...

Page 5: ...haking 8 In the Details portion of the dialog see Figure 3 set the Input Packet Size to the Interface Module s DataTransmit Size Instance EDS parameter 69 value minus 1 byte Similarly set the Output P...

Page 6: ...is sent to In Sight from the PLC Data can be sent between the PLC and the In Sight sensor via the DeviceNet Interface Module using the Input Output spreadsheet functions ReadDeviceNetBuffer and WriteD...

Page 7: ...FormatOutputBuffer Dialog 4 Select another empty cell highlight Input Output from the left pane of the Insert Function dialog select WriteDeviceNetBuffer from the right pane and press the OK button t...

Page 8: ...Cell State of the WriteDeviceNetBuffer function may have to be toggled to initiate a send to the PLC Refer to In Sight Explorer Help Reference for more detailed information on the WriteDeviceNet func...

Page 9: ...the Insert menu and select Function to open the Insert Function dialog 6 Highlight Input Output from the left pane select FormatInputBuffer from the right pane and press the OK button to insert the f...

Page 10: ...n the ReadDeviceNetBuffer function parameters ReadDeviceNetBuffer example In this example assume that the incoming data in the FormatInputBuffer function is as follows An integer is expected at byte 0...

Page 11: ...the NET LED is blinking either the Interface Module was not assigned a Master device or the Master device is not polling it Go into RSNetworx and make sure that it is set up correctly and that the In...

Page 12: ...olation 500 volts ESD protection 10 kv Overload protection 30 volt Short circuit Indefinite Output levels 7 9 volts typical Data size 8 7 bits software configurable Parity Even Odd None Stop bits 1 fi...

Page 13: ...und 6 NC 7 Request to Send 8 Clear to Send 9 NC P N 597 0010 02 Copyright 2001 2008 Cognex Corporation All Rights Reserved All information in this document is subject to change without notice Cognex a...

Reviews: