DeviceNet

®

 Interface Module Installation & Reference 

 

 

Figure 1:  EDS file parameters for In-Sight. 

1.  Configure the Serial I/O parameters (parameters 1-8), including baud rate, bits, and parity. These 

settings must agree with the settings for the In-Sight serial port connected to the Interface 
Module; usually 9600 baud rate, 8 data bits, parity none, 1 stop bit, CTS/RTS (Hardware) Flow 
Control and a Delimiter Mode of Fixed Length. See page 4 for more information on connecting 
the Interface Module to the In-Sight vision sensor. 

2.  Configure the Transmit and Receive sizes. 

a)  Parameter 8: Packet Length. This is the Module receive packet and In-Sight output size; the 

default is 16 bytes. 

b)  Parameter 25: Data Size Instance 1. Parameter #8 + 1 byte, which defines the length of the 

receive byte array. 

c)  Parameter 69. Data Size Instance 1. Parameter #8 + 1 byte, which defines the length of the 

transmit byte array. 

d)  Parameter 49. Set SYNC off (default).

 

e) Press 

Apply

 then 

OK

 to download the changes to the Interface Module.

 

Step 3 – Configure the Master Device 

To configure the Interface Module’s Master Device, use RSNetworx to open the scanner’s property sheet. 

1.  On the Scanlist property tab, add the Interface Module to the Scanlist, if it is not already present. 

2.  Select the Interface Module and click the 

Edit I/O Parameters

 button. The I/O Parameters dialog 

will open. 

a)  Enable the Polled check box. 

b)  Set Rx Size to the receive packet size 

plus

 3 bytes (from the EDS file, parameter #8 + 3). 

c)  Set Tx Size to the transmit packet size 

plus

 3 bytes (from the EDS file parameter #8 + 3). 

d) Click 

OK

 to close the Edit I/O Parameters dialog.

 

 

 

Summary of Contents for CIO-2550-00

Page 1: ...it through DeviceNet to or from a DeviceNet scanner attached to a PLC To set up this connection configure two communications channels one from the In Sight sensor to the DeviceNet Interface Module and...

Page 2: ...S file contained on the DeviceNet Interface Module diskette supplied using the EDS Wizard 2 On the Interface Module set the two rotary MACID switches to the unused MACID you want to assign to the modu...

Page 3: ...stance 1 Parameter 8 1 byte which defines the length of the receive byte array c Parameter 69 Data Size Instance 1 Parameter 8 1 byte which defines the length of the transmit byte array d Parameter 49...

Page 4: ...nd data this changes from a value of 0 to a value of 1 triggering the PLC to send the data to the Interface Module the second byte is a sync byte and the third is the size of data being sent user ente...

Page 5: ...haking 8 In the Details portion of the dialog see Figure 3 set the Input Packet Size to the Interface Module s DataTransmit Size Instance EDS parameter 69 value minus 1 byte Similarly set the Output P...

Page 6: ...is sent to In Sight from the PLC Data can be sent between the PLC and the In Sight sensor via the DeviceNet Interface Module using the Input Output spreadsheet functions ReadDeviceNetBuffer and WriteD...

Page 7: ...FormatOutputBuffer Dialog 4 Select another empty cell highlight Input Output from the left pane of the Insert Function dialog select WriteDeviceNetBuffer from the right pane and press the OK button t...

Page 8: ...Cell State of the WriteDeviceNetBuffer function may have to be toggled to initiate a send to the PLC Refer to In Sight Explorer Help Reference for more detailed information on the WriteDeviceNet func...

Page 9: ...the Insert menu and select Function to open the Insert Function dialog 6 Highlight Input Output from the left pane select FormatInputBuffer from the right pane and press the OK button to insert the f...

Page 10: ...n the ReadDeviceNetBuffer function parameters ReadDeviceNetBuffer example In this example assume that the incoming data in the FormatInputBuffer function is as follows An integer is expected at byte 0...

Page 11: ...the NET LED is blinking either the Interface Module was not assigned a Master device or the Master device is not polling it Go into RSNetworx and make sure that it is set up correctly and that the In...

Page 12: ...olation 500 volts ESD protection 10 kv Overload protection 30 volt Short circuit Indefinite Output levels 7 9 volts typical Data size 8 7 bits software configurable Parity Even Odd None Stop bits 1 fi...

Page 13: ...und 6 NC 7 Request to Send 8 Clear to Send 9 NC P N 597 0010 02 Copyright 2001 2008 Cognex Corporation All Rights Reserved All information in this document is subject to change without notice Cognex a...

Reviews: