background image

 

DeviceNet

®

 Interface Module Installation & Reference

 

3. 

On the scanner’s property sheet: 

a) Select 

the 

Input Data Table 

tab and either manually map the Interface or Automap the 

Interface. 

b) Select 

the 

Output Data Table 

tab and either manually map the Interface or Automap the 

Interface. 

4.  Download the changes to the Scanner.

 

5.  Reboot the PLC. At this point, you should see a solid green light on the Interface Module for both 

the MOD and NET lights.

 

Both input and output mappings allocate the Rx and Tx sizes set in the previous step for the PLC’s data 
tables. In the PLC, the first two bytes of the mapping are synchronization and trigger bytes, and the next 
byte is the data transmission size. For example, using the default values of 16 for both Input and Output 
packet sizes, the Rx and Tx I/O sizes should both equal 19 bytes. In the Rx PLC mapping, the first two 
bytes are the synchronization bytes, the next byte is the receive size, 0x10 (16), and the remaining 16 
bytes are the data received. In the Tx PLC mapping, the first byte is a trigger to send data (this changes 
from a value of 0 to a value of 1, triggering the PLC to send the data to the Interface Module), the second 
byte is a sync byte and the third is the size of data being sent (user entered, default 0x10 or 16 bytes 
decimal) and the remaining 16 bytes are the data to be sent with each change to a value of 1 of the first 
overhead byte. 

NOTE: 

The Allen-Bradley RSLogix Input and Output display windows swap the bytes in each 16-bit word. 

Connecting the Interface Module to In-Sight 

This section describes how to connect the Interface Module to the In-Sight sensor, and how to configure 
the In-Sight serial ports for DeviceNet communication. 

Step 1 – Connect the Interface Module to In-Sight 

1.  Remove the power connector from the In-Sight sensor. 

2.  Plug the I/O module cable (DB15 connector) from the sensor into a Breakout or CIO module. 

3.  Plug one end of the RS232 serial cable into a Breakout or CIO module’s RS232 port. Plug the 

other end of the RS232 serial cable into the Interface Module’s 9-pin RS232 connector. 

4.  Re-connect power to the In-Sight sensor and configure the In-Sight user interface for the Interface 

Module. 

5.  From the Sensor menu, select

 Serial Port Settings

 to open the Serial Port Settings dialog (see 

Figure 2). 

4  

 

Summary of Contents for CIO-2550-00

Page 1: ...it through DeviceNet to or from a DeviceNet scanner attached to a PLC To set up this connection configure two communications channels one from the In Sight sensor to the DeviceNet Interface Module and...

Page 2: ...S file contained on the DeviceNet Interface Module diskette supplied using the EDS Wizard 2 On the Interface Module set the two rotary MACID switches to the unused MACID you want to assign to the modu...

Page 3: ...stance 1 Parameter 8 1 byte which defines the length of the receive byte array c Parameter 69 Data Size Instance 1 Parameter 8 1 byte which defines the length of the transmit byte array d Parameter 49...

Page 4: ...nd data this changes from a value of 0 to a value of 1 triggering the PLC to send the data to the Interface Module the second byte is a sync byte and the third is the size of data being sent user ente...

Page 5: ...haking 8 In the Details portion of the dialog see Figure 3 set the Input Packet Size to the Interface Module s DataTransmit Size Instance EDS parameter 69 value minus 1 byte Similarly set the Output P...

Page 6: ...is sent to In Sight from the PLC Data can be sent between the PLC and the In Sight sensor via the DeviceNet Interface Module using the Input Output spreadsheet functions ReadDeviceNetBuffer and WriteD...

Page 7: ...FormatOutputBuffer Dialog 4 Select another empty cell highlight Input Output from the left pane of the Insert Function dialog select WriteDeviceNetBuffer from the right pane and press the OK button t...

Page 8: ...Cell State of the WriteDeviceNetBuffer function may have to be toggled to initiate a send to the PLC Refer to In Sight Explorer Help Reference for more detailed information on the WriteDeviceNet func...

Page 9: ...the Insert menu and select Function to open the Insert Function dialog 6 Highlight Input Output from the left pane select FormatInputBuffer from the right pane and press the OK button to insert the f...

Page 10: ...n the ReadDeviceNetBuffer function parameters ReadDeviceNetBuffer example In this example assume that the incoming data in the FormatInputBuffer function is as follows An integer is expected at byte 0...

Page 11: ...the NET LED is blinking either the Interface Module was not assigned a Master device or the Master device is not polling it Go into RSNetworx and make sure that it is set up correctly and that the In...

Page 12: ...olation 500 volts ESD protection 10 kv Overload protection 30 volt Short circuit Indefinite Output levels 7 9 volts typical Data size 8 7 bits software configurable Parity Even Odd None Stop bits 1 fi...

Page 13: ...und 6 NC 7 Request to Send 8 Clear to Send 9 NC P N 597 0010 02 Copyright 2001 2008 Cognex Corporation All Rights Reserved All information in this document is subject to change without notice Cognex a...

Reviews: