Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
/
CLVR04Z / CLVR08Z / CLVR12Z
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
35
5. Auxiliary Output of 30V:
Output of 30V monitored and protected by a fuse, which powers sounders,
electromagnets of fire doors, etc.
NOTE: Monitoring of this output is only for crossed line.
6. Batteries output:
The batteries output, monitored and protected by a fuse, allows the batteries to be
connected to the control panel.
Through this connection, batteries are charged and their condition monitored.
This output is protected against reverse polarity.
The capacity of the batteries connected to the control panel will depend on the number
of zones and additional charges (e.g. Sounders, door electromagnets and fire doors,
etc.). The use of 7 Ah batteries is recommended.
7. Fuses:
CLVR02Z, CLVR04Z, CLVR08Z y CLVR12Z Control Panel
Batteries fuse
FUS2 / FUS3
1)
4
A
Fuse 30V
Autoresettable Fuse
0,75 A / 1,5 A
1)
Fuse S1
Autoresettable Fuse
1 A / 1,85 A
1)
Fuse S2
Autoresettable Fuse
1 A / 0,75 A
1)
1)
CLVR08Z and CLVR12Z have this designation / Value.
8. Electrical power supply input 110~230 Vac:
The three 110~230 Vac (phase, neutral and earth) power supply terminals must be
connected to the control panel.
9. Wiring:
For wiring of the system, all the outputs must be 2 x 1,5 mm cable, BRAIDED AND
SHIELDED HALOGEN FREE for distances up to 800 m. For higher distances up to 1500
m, 2 x 2,5 mm cable, BRAIDED AND SHIELDED HALOGEN FREE must be necessary.