Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
/
CLVR04Z / CLVR08Z / CLVR12Z
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
31
Control keys
are described hereafter:
KEY
DESCRIPTION
Selection of a zone, to modify its condition. Accessible from access level 2.
►
1 pressing
All the alarm leds will flash.
►
Subsequent pressings
Selected zone changes (only led of that zone will
flash).
Check condition of indication lamps/buzzer of the control panel. Also allows control
panel to be reset. Accessible from access level 2.
►
1 pressing
Activates buzzer and all LEDs.
►
Press constantly
Resets control panel.
►
1 pressing: When a zone or relay is selected, it goes back to the state prior to
selection.
Reference of software version and configuration version of delays. Firstly access
level 3 must be entered.
►
1 pressing
Buzzer is activated first and then all LEDs. Then the software
version is shown. Then the delay configuration version.
Selection of relay. Accessible from access level 2.
►
1 pressing
All relay LEDs will flash (Sounder & Fault).
►
Subsequent pressings
Changes the selected relay (only that LED will flash)
Deactivation of the acoustic signal of the control panel due to alarm or fault.
Accessible from access level 1.
►
1 pressing
switches off the sounder noise. In the event of a new incident, the
buzzer will activate automatically.
Locking/unlocking of the general sounder. Accessible from access level 2.
►
1 pressing
Locking/Unlocking of the general sounder output whether in alarm
mode or not.
Locking/unlocking of the delay of all outputs. Accessible from access level 2.
►
1 pressing
Locks /unlocks the delay of all outputs (general sounder & fault).
Selection of configuration times of delays. First must enter access level 3 and
select a relay (see key 3).
►
1 pressing
Indication of the current delay.
►
Subsequent pressings
Changes delay time selection.
Enabling/disabling of zone. First must enter access level 2 and select a zone (see
key “1”).
►
1 pressing
Disables/enables selected zone.
Enabling/disabling of test mode of a zone. First must enter access level 2 and
select a zone (see key “1”).
►
1 pressing
Enables/disables test mode in the selected zone.
selección zona
zone selection
1
reset / autotest
2
selección relé
relay selection
3
4
5
6
sin retardo
no delay
7
desconexión
general disable
8
modo pruebas
test mode