Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
/
CLVR04Z / CLVR08Z / CLVR12Z
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
47
9.1.2.4.
Test of the 30 V auxiliary output
In order to check that the 30 Vdc auxiliary output function is working properly, it is only
necessary to check that its output has 30 Vdc.
9.2. Testing of the detection elements
9.2.1. Testing Mode of the detection elements
The control panel has a mode of operation that allows the detectors and manual call points in a
zone to be checked easily, given that the zone is reset automatically 20 seconds after the alarm
triggers.
In this test mode, all the control panel relays are disabled, therefore no signal of any kind will be
sent outside the control panel.
Note:
If the detector or call point alarm persists after the automatic reset time, the control panel
will enter in fault mode activating the buzzer and the leds “D” and “G”.
In order to gain access to or exit from this Test Mode the following must be done:
4) Activate access level 2 (press the control keys once in the following order:
Zone
Selection, Reset/Autotest, Zone Selection, Reset/Autotest
).
5) Select the zone required for testing using the control key
Select Zone
.
6) Press
the
Test Mode
control key.
Note:
Enabling/disabling of the Test Mode of the zone is indicated on the control panel
through the flashing/disabling of the test/disable “R” indicator led (see chapter 2.1.1).
Figure 16: Keys and indications used for testing of the detection elements