It is recommended that the fire is inspected/serviced
annually by a competent person (e.g. A Corgi Registered
Installer).
It is recommended that the flue is checked for debris.
Turn off the gas supply before commencing any servicing.
After any servicing
ALWAYS
check for gas soundness
and carry out a spillage test as detailed in the section
‘CHECK FOR CLEARANCE OF PRODUCTS OF
COMBUSTION’.
RE-ASSEMBLE PARTS IN REVERSE ORDER.
At yearly intervals, turn off and allow to cool down. Check
all coals, pilot burner/ignition burner unit, for soot/debris
deposits. These can cause imperfect flame appearance
and should be removed by lightly vacuuming. Replace all
misplaced coals and re-light.
NOTE:
On failure of either the pilot burner/ignition unit or
main control valve, repairs should be carried out by a
competent person.
For LPG Appliances Only
Because of the nature of L.P. Gases, there could be
excessive soot particles deposited on the refractories,
therefore it is recommended that this should be checked
at six monthly intervals, by turning off and allowing to
cool down. Check all coals, pilot/ignition unit for soot or
debris deposits. These can cause imperfect flame
appearance and should be removed by lightly vacuuming.
Replace all misplaced coals and re-light.
RENEWING PILOT BURNER/IGNITION UNIT - SEE
FIG. 28
1. Isolate gas supply.
2. Remove all coals and store in a safe place.
3. Disconnect main 8mm gas supply pipe from restrictor
valve.
4. Loosen and remove 2 clamping brackets. See Fig. 12.
5. Remove firebed from appliance by pushing up from
underneath, tilt forward to clear spindle and tap from
front of support tray. Lift fire bed clear of appliance.
6. Undo and remove the thermocouple nuts from the
rear of the control valve.
7. Disconnect and remove piezo ignition wiring from
ignition electrode.
8. Undo and remove the gas supply pipe from the
bottom of pilot burner.
9. Undo and remove 2 x 4mm locating nuts or studs on
pilot/ignition unit. Remove unit.
10. Replace with new unit and reassemble in reverse
order. Ensure coals are positioned as in section
‘LAYING THE FUEL BED’.
RENEWING CONTROL VALVE - SEE FIG. 28
1. Proceed as Steps 1 to 5 in section ‘RENEWING PILOT
BURNER/IGNITION UNIT’.
2. Undo and remove the main burner gas supply pipe.
3. Undo and remove pilot gas supply pipe located on the
body of the main valve.
4. Remove control knob by pulling firmly.
5. Remove control knob cover.
6. Remove main valve unit by removing 2 x 4mm
securing screws .
7. Replace with new unit and reassemble in reverse
order.
SERVICING
SERVICING PROCEDURE
26
DESN 512261
FIG. 28
CONTROL
KNOB
CONTROL VALVE/
PIEZO UNIT
OXYPILOT
ASSEMBLY.