EVAC-500 Voice Alarm & Evacuation System Operation Manual
8
/
42
Note: Note: please connection at least one zone of speaker circuit after completing the wiring. It will be OK when not all
speaker zones output are connected with speakers. Please also ensure the total speaker loading is less than 80% of the
host built-in amplifier loading.
3- Six 24V Relay Output
external four wire system programmable;
rated output current for each road: 0.2 A;
Note: output shall not be greater than the total power 28 w;
4-8 Program Control Outputs.
These outputs usually shall be keep open, which could be programmed in the software to activate it or terminate it
auto or manually.
5-8 Program Control Inputs.
These inputs usually shall be keep open, which could be programmed in the software to activate it or terminate it
auto or manually.
6-LAN Input for PC Software.
It is
mainly used to connect to EVAC-500SF for setting, program and manual operation.
Note
:
1) Default IP address: 192.168.1.168, Communication port number: 16888.
2) Reset the IP address to default by enable & disable once time the dipswitch 6
th
PIN on the rear panel of host.
3) If you dislike the default IP address, please up the 5
th
dipswitch to open DHCP function. Make sure your
network router opened up the DHCP function. This function is mainly used to upgrade new features to use in the
future, the current system before unplug ";
4) Support PC software directly connection to EVAC-500
,
automatic identify cross and straight cable. All
communication cable shall be meet TIE/EIA-568B standards including connection to extension and remote paging
microphone.
7- Two RJ45 Communication Ports.
Use straight CAT6 cable to connect the extension controller EVAC-500RT to the host, system capacity of 19 units
extension and communication distance is up to 600 meters. Support microphone loop connection or star connection as
above remote paging microphone pictures, the system software will auto distinguish different kinds of cable connection.
Also connection ports for extend EVAC-500RM/EVAC-500FM/EVAC-500TM/EVAC-500RT
support loop connection or start connection(as shown in the figure below), automatic identification of software
- to maintain the operation of the system is reliable & stable recommend to use the loop connection.
Closed or loop connection mode
Star connection