background image

EVAC-500 Voice Alarm & Evacuation System Operation Manual 

 

3

 / 

42

 

 

System Overview 
 

The EVAC-500 voice evacuation system is EN54-16 certified public address & voice evacuation system. The all in one 
voice alarm & evacuation controller built-in remote PC software, zone paging controller, all main signal line monitoring, 
amplifier changeover, speaker line supervision, power supply monitoring and power amplifier, voice recorder, SD card, 
emergency microphone and fire alarm interface. The voice evacuation controller is innovated with DSP (digital signal 
processor) to ensure its hi-fi audio performance and superior signal processing in case of commercial announcement 
and emergency evacuation. Each controller built-in 6 zone speaker outputs, rated power output at 500W or 240W. The 
voice evacuation controller shall be pre-set through the supplied software over microphone number, zone number, zone 
loading,  speaker  monitoring,  fire  alarm  mode,  alert/EVAC  message  zone  output,  AC/DC  etc,  then  synchronized  the 
setting  to  master  controller  and  router.  The  voice  evacuation  system  is  strictly  follow  the  Construction  products 
Regulation

EU

No 305/2011: EN54-16:2008 Voice Alarm Control and Indicating Equipment. 

 
Feature: 

  EN54-16 certification No. I/ISEETC. 000620190305. 

  Digital voice evacuation system all in one solution. 

  Integration of voice evacuation controller, remote PC software, zone paging controller, all main signal line 

monitoring, amplifier changeover, speaker line supervision, power supply monitoring and power amplifier, voice 
recorder, SD card, emergency microphone and fire alarm interface. 

  Auto broadcasting EVAC and alert 256 voice messages to pre-set zones. 

  Customized alert, evacuation & business message stored at SD card. 

  AB speaker line surveillance to avoid any speaker line failure. 

  Back-up power amplifier management. 

  Up to 120 zones by cascaded more router EVAC-500RT. 

  Support 32 units of remote paging microphone EVAC-500RM & EVAC-500TM. 

  Support external connection of fireman microphone EVAC-500FM. 

  Redundant network cabling backup through CAT6 cable loop connection. 

  8 supervised control inputs & 8 control outputs, 1 fault, 1 reset & 1 EVAC relay outs. 

  Logs and fault events auto recording. 

 

System Capacity-120 Zones: 

 

   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for EVAC-12KD

Page 1: ...Digital Voice Alarm Evacuation System EVAC 500 EVAC 240 EVAC 500RT EVAC 240RT EVAC 500FM EVAC 500TM EVAC 500RM EVAC 12KD EVAC 500SFT INSTALLATION AND OPERATION MANUAL ...

Page 2: ... System Operation Guidance 23 27 5 1 Background Music System Broadcast 23 5 2 Manual Emergency Broadcast 23 5 3 Auto Emergency Broadcast 24 5 4 Emergency Microphone Announcement 24 5 5 General Announcement From Remote Microphone 24 5 6 BGM Broadcast Microphone Announcement from Software 24 28 5 6 1 Via Software BGM Broadcast 26 5 6 2 Via Software Microphone Broadcast 28 6 System Software EVAC 500S...

Page 3: ...nal technician after training of voice alarm evacuation system 3 Terminology Host EVAC 500 or EVAC 240 Extension host EVAC 500RT or EVAC 240RT Remote Microphone EVAC 500RM Touch screen remote Controller EVAC 500TM Fireman s Microphone EVAC 500FM Keypad EVAC 12KD The software of this system will be continuously upgraded but backward compatibility Please note the company s website real time informat...

Page 4: ...to master controller and router The voice evacuation system is strictly follow the Construction products Regulation EU No 305 2011 EN54 16 2008 Voice Alarm Control and Indicating Equipment Feature EN54 16 certification No I ISEETC 000620190305 Digital voice evacuation system all in one solution Integration of voice evacuation controller remote PC software zone paging controller all main signal lin...

Page 5: ...h 6 external microphone or line inputs for analog microphone use or external audio sources input With control input and control output to inter work with third party system With 3000 events history record includes power module fireman mic EVAC message amplifier speaker line System capacity of 32 units remote paging microphone up to 600 meters through CAT6 straight cable System support redundancy w...

Page 6: ...recorded and inquired in the software history record 8 ACK RESET Button a If the system various modules work normal or abnormal system module diagnosis but press the button when the indicator FAULT light is not flashing equipment do not do any processing b If the system module in the diagnosis of abnormal FAULT of FAULT indicator light flashing press some button FAULT stopped lighting from blinkin...

Page 7: ...ges and inform the user in the form of light Zone detection sensitivity is more than 20W 14 Paging Indicator When paging can manually close the zones where no need paging or add new zones 15 EVAC ALERT Indicator When EVAC and alert emergency broadcast is working the indicator will be light on 16 BGM Indicator When background music broadcast is working the indicator will be light on Note Manual bro...

Page 8: ...UPS or equivalent product Note 1 Use EN54 4 certificated power supply when EN standard required 2 Do make sure the 24V DC could meet the minimum working current of the host For example full loading of EVAC 500 at 500W the lead acid battery shall supply the current higher than 27A battery capacity higher than 27Ah and working time shall be full loading 27Ah 1 2 hours 2 Six A B Speaker Zone Output e...

Page 9: ...le once time the dipswitch 6 th PIN on the rear panel of host 3 If you dislike the default IP address please up the 5 th dipswitch to open DHCP function Make sure your network router opened up the DHCP function This function is mainly used to upgrade new features to use in the future the current system before unplug 4 Support PC software directly connection to EVAC 500 automatic identify cross and...

Page 10: ...power amplifier interface power signal inputs of 100V or 70V audio signal output shall be balanced 11 System Fault Output In case of any fault for the system this output will closed circuit to trigger output and normally default is open circuit 12 System EVAC State Output In case of EVAC the output will closed circuit to trigger output and normally default is open circuit 13 Emergency Reset Input ...

Page 11: ... reset the host IP address from its default IP address 192 168 1 168 and port number is 16888 Only ensure the software PC s IP address is same gateway with the host IP address thus the communication and program could be well done 7 Impedance Calibration means to calibrate the zone speaker loading impedance after the software program of speaker impedance value and fluctuation percentage then the sy...

Page 12: ...Control Input Output Fault Output Closed circuit no voltage EVAC State Output Closed circuit no voltage EVAC Reset Input Closed circuit no voltage T 0 5s 8 Program Control Output Closed circuit no voltage 8 Program Control Input Way 1 Closed circuit no voltage Way 2 Level input and max 3 3V Emergency Message Format WAV Memory Card SD memory card Capacity 32G Message No 255 Max Period 10 years SD c...

Page 13: ...he fireman s microphone is a surface mounted cabinet containing a first help and echo cancelling microphone state indicator pre recorded message announcement and live announcement The fireman s microphone is typically used in case of emergency to help the fireman to enter or acknowledge the emergency state and acknowledge and reset the fault state Emergency or alert pre recorded messages can be br...

Page 14: ...EVAC 500 Voice Alarm Evacuation System Operation Manual 13 42 2 1 Front Panel and Rear Panel ...

Page 15: ... mode to terminate the emergency broadcast and terminate the zone output b Input a reset signal to the emergency control input terminal on the rear panel of the EVAC 500 which has been assigned a reset function These events history could be recorded and inquired in the software history record 6 FAULT ACK a If the system various modules work normal or abnormal system module diagnosis but press the ...

Page 16: ...d means start the LED indication test all LED indicator will be from red green yellow then to normal state Below is example of remote paging mic ID from No 1 to No 4 2 2 Technical Specifications Electric Part Phantom Power Voltage 20V 27 5V Maximum Current Less than 0 2A 24V power supplier all the LED on the front panel will be lighted up it is paging state Power Consumption Less than 3W Performan...

Page 17: ...4 16 certified and designed exclusively for EVAC 500 public address voice evacuation system The remote microphone is used for business and commercial live announcement to selected zones or all zones The remote microphone is designed of 120 zone with busy working indicators Up to 32 units of remote microphone could be connected to the voice evacuation system via shielded CAT6 cable and RJ45 connect...

Page 18: ...can select the all zone button 4 Talk button When the user confirms the selection of the zone press this talk button on LCD screen or press talk button to make announcement Note When the gooseneck is ready for talk there is round ring indicator will be illuminated 5 Monitor speakers Used to monitor the user s current paging sound this output can be closed and open through the interface and the vol...

Page 19: ...e presence of line input priority 9 Main power switch on off 10 External 24V DC Power Supply Input Note When the device and the host communication distance is longer than 100m please use external power supply specifications 24VDC 1A 3 2 Technical Specifications Electrical Specifications Phantom power voltage 20V 27 5V maximum current less then 0 5A 24VDC front panel LED lighting Paging state Power...

Page 20: ...600 meters Power supply from EVAC 500 controller Description The EVAC 500RM remote microphone or call station is EN54 16 certified and designed exclusively for EVAC 500 public address voice evacuation system The remote microphone is used for business and commercial live announcement to selected zones or all zones The remote microphone is designed of 12 zone buttons with busy working indicators One...

Page 21: ...uipment is busy please wait Off normal state can be used to call or control the specified partition 2 Microphone XLR Socket Connection with the supplied gooseneck microphone 3 Zone Status Indicator On indicates that its current partition is in working condition Flashing indicates that the user is currently selecting this partition Off indicates that the partition is currently not working handle th...

Page 22: ... refers to the description in the later 11 7 Main Power switch to on off the power supply for this microphone 8 Two RJ45Network Interface There are two RJ45 communication ports one for host and the other port is for next remote microphone hand in hand connection or loop connection back to the host for redundancy connection For these two RJ45 ports there is no distinction between the primary and th...

Page 23: ...en the EVAC 500TP terminal matching resistor by this way the system connection can be non loop 2 Similar to the Pic Two of the loop connection it is need to prohibit all external devices terminal resistance so the system loop connection is recommended for more stable performance 4 2 Technical Specification Model EVAC 500RM Description Remote Paging Microphone System Capacity 32 units Communication...

Page 24: ... The electrical connection between the system equipment is correct and working properly 5 1 Background Music Broadcast Input the audio sources or microphone to the line input1 6 on rear panel select the line input through the source selector on the front panel of host or extension unit open the zone output with corresponding BGM indicator means background music broadcast Note The emergency message...

Page 25: ...phone Announcement Press the clip of emergency microphone to make emergency announcement to all zone any time the pre announcement chime will be broadcast first and the EMG microphone indicator will light on means ready for emergency announcement hang off the microphone to terminate the broadcast This emergency microphone circuit will be real time supervised 5 5 General Announcement from Remote Mi...

Page 26: ...EVAC 500 Voice Alarm Evacuation System Operation Manual 25 42 ...

Page 27: ...device built in background music playback mode currently only supports single loop and all files in this folder loop According to the diagram above 1 11 after configuration is complete please click on the 12 in the Address for the EVAC 01 500 FM the need to Address the assignment TYPE Fire the paging the EVAC RM by default Business the paging or EVAC 500 tp to press the button 01 can be the host o...

Page 28: ...the user need to be effectively required to synchronize the system host that is click Application ii When you complete the configuration above you can control it by following the image below The diagram above shows and operates 1 To configure all groups by I click on the corresponding grouping name and the 2 on the right shows the partitions contained in the current grouping 2 The partitions curre...

Page 29: ... Software EVAC 500SFT Microphone Announcement Emergency microphone on the front panel of the host is monitored it is mainly used for all zone emergency announcement select the zone all keys then there is chime for reminding after that push the clip of the emergency microphone to initiate the announcement and push the clip again with one chime to terminate the announcement Operation on EVAC 500RM i...

Page 30: ... 500 host Give up the action Current zone is prohibited for operation Current Zone is working Zone impedance vibration open circuit or short circuit The current zone is normal no broadcast The current zone is under emergency broadcast The current system modules normal The current system module faulty The current host normal The current host system is faulty Refresh Upload Save Host Host 01 means E...

Page 31: ...istrator otherwise it may lead to the error during the software installation and during the running after installation Please check whether the administrator authority is obtained before running by below method Click on the icon EVAC exe by right mouse to select the properties to run as administrator Keep the PC and Host EVAC 500 in the same network Gateway Only after change the PC s IP address sa...

Page 32: ...exe icon on desktop to log in the main operation page of the software Click on to enter user name password for identity verification The software will be auto exist once 3 times wrong password input Default user name is Admin and password is blank or no need password directly click OK to log in 1 This password can be modified through the OTHER user and password at left side after the login 2 Wrong...

Page 33: ... system diagram Manage include firmware download No change network adapter Edit the IP address empty all log clear the log in event and software security Password is need to exist Help is used to check the software version 1 System Menu Reflash refreshes the up to date status of the interface in which current user is located Import is used to import from voice alarm controller to the management so...

Page 34: ... error of EVAC 500 system the percentage more larger means accuracy is more lower 6 3 4 Zone Control Configuration Login software or click the left CONTROL as picture 1 above it shows message as below In the left shows that they are six group in EVAC 500SF On the right shows that they are six zone in current system The red LED on the top of right indicate current system worked at emergency model T...

Page 35: ...rom the right middle will indicated the zones of the current group To choose the output audio use the mouse to click EVAC MESSAGE it need on emergency status or LINEINPUT AUDIO audio on the right side All system zones control for sure it will be the same result if you put all the system zones to one group or multi groups Choose the target zone Click all zones then choose output audio Click EVAC ME...

Page 36: ...he drop down list box appears in the figure otherwise the change is invalid Note After the modification is complete double click in the blank area make sure that no drop down list box in the box appears in the list box click OK otherwise the change is invalid Similarly the user can through the Paging prompt tone switch setting for each of the microphone switch and specify a different prompt bell m...

Page 37: ...ion 4 extended host number from 02 the user can not change that is the user in the address of 01 if you use a microphone on grouping mode the elected group 01 paging is equivalent to choose the host and at the same time extend the host 01 each five partitions paging Note After the modification is completed please click Application otherwise your Settings will not be able to complete your expected ...

Page 38: ...set the output partition and the EVAC information parameters of the output are determined by the contact setting interface above 3 Neighboring mode Once the Trigger Inputs from the host or extended host enter the fire alarm signal wait After setting the delay time output the EVAC voice information to the corresponding partition of the current contact and Play the Play mode in the right image play ...

Page 39: ... information after the trigger after the trigger of the voice information will not play but after the trigger fire will be superimposed on the output of EVAC voice information 3 When Alarm mode is selected as Neighboring mode EVAC and ALERT information must be selected the user can not modify has triggered the partition system automatically superimposed on the current output of the fire zone 6 3 6...

Page 40: ...and add all zone to the current group Note Please click Application after modify or your setting will not be successful 6 3 7 Priority Configuration Click SYSTEM CONFIGURATION then click Audio priority as below See Pic above ID number is automatically added by system AUDIO NAME is the audio in the host PRIORITY means audio s priority but it also directly affect of the output permission of current ...

Page 41: ...scription User can check designated time recording though Log type and and click on tooling bar to save the log as excel sheet 6 3 9 OTHER 1 Change password 2 Correct system time 3 Adjust speaker zone impedance 6 3 9 1 Change user password Click User and password user input password If wrong system will quit automatically Password correct will show as below Description USER NAME Means name of the ...

Page 42: ...ing as below Description Data and Time means date and time display time is the current computer time Auto for EVAC 500SF automatic proofreading the host of time Note After edition please click Application otherwise your settings can not be completed 6 3 9 3 Speaker Impedance Error Adjustment Click EVAC system timing Select allowed error range of current speaker circuit from the drop down list box ...

Page 43: ... lines please set configuration accordingly to your requirements If major fault cause system not working please contact our After Sales Service for Repair processing Built in accessories Do not dismantle machine without permission in order to avoid the equipment or module s permanent damage and electric shock hazard 7 In order to ensure reliable work please ensure a good ground connection 8 After ...