Page 24 - FL-20A Instruction Manual
Model FL-20A Cable Fault Locator
Calibration
A 20KV DC Voltage Divider and a DC multimeter are required to calibrate the
FL-20A. Metering equipment MUST be able to withstand 20kVDC.
Caution.
It is imperative that only personnel trained in the dangers of high voltage
operate this equipment.
A stored charge in a test cable can kill!
A charge
can remain in a cable if the cable has not been properly discharged, even
when it is no longer attached to the FL-20A.
Calibrate the FL-20A Output Voltage
The FL-20A Output Voltage is measured on the DC multimeter.
1. Press the Calibration button, which is found on the second page
of the Settings menu.
2. As directed, short all three probes (red, blue, and green) together
using a piece of copper or brass rod. Locate the green 2-pin
connector shipped with the FL-20A. Add a jumper between the
two pins. Insert the connector into the FL-20A 2-pin exter-
nal interlock terminal block, which is located on the back of
the unit. You cannot proceed without installing the connector.
Press NEXT.
3. The number displayed above CURRENT will be chang-
ing. Wait about 10 seconds and press the LOCK button. The
CURRENT number will be saved to the CENTER number.
The typical acceptable range is 12,000 to 15,000. Press NEXT.
4. Connect the shorted red and blue probes to the input of your
DC multimeter.
5. Connect the green ground probe to earth ground. Check that
the ground connection on the rear of the FL-20A is secure and
connected to earth ground. Press NEXT.
6. The red high voltage light on the X3A will illuminate, indi-
cating that there is high voltage on the red and blue probes.
DANGER!
Do not touch the red and blue probes for the
remainder of the calibration procedure, because they are
charged.
7. As directed on the touch screen, use the DOWN ADJ and UP
ADJ buttons so that the multimeter displays 1.0 kV (within 2%
or +/- 20 volts). Press NEXT.
8. A new screen will appear. View the reading on the multimeter.
If necessary, use the DOWN ADJ and UP ADJ buttons on the
touch screen until the multimeter displays 15.0 kV (+/- 2% or