Model FL-20A Cable Fault Locator
during the test. The default setting is OFF.
Vmax (kV)
This is the maximum Hi-Pot test voltage. The range is 1.0kV to 20.0kV.
This setting can be changed here to affect all Hi-Pot tests, or at the time
of test if Lock Hi-Pot Settings is OFF.
Vsteps (#)
This is the number of steps the Hi-Pot test will take to get to Vmax
(kV), the maximum Hi-Pot voltage. The number is between 2 and 20.
This setting can be changed here to affect all Hi-Pot tests, or at the time
of test if Lock Hi-Pot Settings is OFF.
Vramp Time (s)
This setting is found on page 2 of the Hi-Pot parameters menu. This is
the time, in seconds, up to 60 seconds, that the FL-20A will take to per-
form each Vstep to get to the preset maximum Hi-Pot voltage (Vmax
(kV)). This setting can be changed here to affect all Hi-Pot tests, or at
the time of test if Lock Hi-Pot Settings is OFF.
Vhold Time (s)
This is the time, in seconds, that the FL-20A will stay at Vmax (kV), the
maximum test voltage, before the test ends. The maximum Vhold Time
(s) is 60 seconds. This setting can be changed here to affect all Hi-Pot
tests, or at the time of test if Lock Hi-Pot Settings is OFF.