8.7
Malfunction codes and possible solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
Solution
AL
01
Smoke thermostat
- Contact the Technical
Assistance Centre
AL
02
Low water pressure in
system
- Restore pressure
- Check for any leaks in
the system
AL
04
Domestic hot water sen-
sor fault
(return sensor
fault for T models)
- Check connections
- Check the sensor is
working
AL
05
Delivery sensor fault
- Check connections
- Check the sensor is
working
AL
06
No flame detection
- Check the integrity of
the electrode and check
that it is not grounded
- Check gas availability
and pressure
- Check the integrity of
the gas valve and the
card
AL
07
Sensor or safety thermo-
stat intervenes
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or
the thermostat
- Check that the pump
impeller is not blocked
AL
08
Fault in the flame de-
tection circuit
- Check the integrity of
the electrode and check
that it is not grounded
- Check the integrity of
the gas valve and the
card
AL
09
No water circulating in
the system
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
AL
11
Gas valve modulator
disconnected
- Check the electrical
connection
AL
12
Domestic hot water sen-
sor fault in tank mode
- Set the parameter tS 0.4
(Combustion configura-
tion) to 1
AL
17
Fault regarding maximum
deviation between the 2
NTC heating sensors
- Replace the dual sensor
AL
28
Maximum number of con-
secutive resets reached
- Wait 1 hour and try
unblocking the board
again
- Contact the Technical
Assistance Centre
AL
37
Fault due to low network
voltage
- Check the voltage
- Contact your network
provider
AL
40
Incorrect network fre-
quency detected
- Contact your network
provider
AL
41
Flame loss more than 6
consecutive times
- Check the ignition/de-
tection electrode
- Check the gas supply
(open valve)
- Check mains gas
pressure
AL
42
Button fault
- Check that buttons are
working
AL
43
Open Therm communica-
tion fault
- Check the OT electric
connection
AL
44
Gas valve timeout fault
without flame
- Check gas valve and
board
AL
62
The self-calibrating pro-
cedure must be carried
out
- Carry out the self-cali-
brating procedure (see
the specific section)
Type
No.
Fault
Solution
AL
72
Incorrect positioning of
the delivery sensor
- Check delivery sensor
operation and position
AL
74
Second delivery sensor
fault
- Check second delivery
sensor operation and
position
AL
80
Fault on the valve control
logic line/valve cable
damaged
- Check gas valve and
board
AL
81
Block due combustion
during start-up
- Check for blockage in
chimney
- Check air diaphragm
(for BF models)
- Check gas calibration
- Bleed the air from the
gas circuit
AL
83
Irregular combustion
(temporary error)
- Check for blockage in
chimney
- Check air diaphragm
(for BF models)
- Check gas calibration
AL
88
Internal error (board
component protection)
- Check the board is
working
- Replace board
AL
96
Block due to clogging in
smoke outlet
- Check for blockage in
chimney
- Check the smoke outlet
and electrode posi-
tion (not touching the
burner)
-
-
Frequent relief valve
intervention
- Check circuit pressure
- Check expansion vessel
-
-
Limited production of
domestic hot water
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot
water circuit valve
8.7.1
Maintenance request
When it is time to perform maintenance on the boiler,
"SE"
shows
on the display.
Contact the technical assistance service to organise the necessary
work.
Summary of Contents for 24 BF
Page 10: ...10 FR ...
Page 49: ...49 FR ...
Page 58: ...58 EN ...
Page 97: ...97 EN ...
Page 98: ...98 ...
Page 99: ...99 ...
Page 100: ...Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 ...
Page 101: ...Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 ...
Page 102: ...51 ...
Page 103: ...50 ...
Page 104: ...49 ...
Page 143: ...10 ...