4

English 09/02

DESCRIPTION OF STANDARD UNIT

These air cooled chillers with axial-flow fans and cycle

reversal operate with R22 refrigerant fluid (HRAT-HRAN)

or R407c refrigerant fluid (HRAT E), and are designed for

external installation. The units conform to the essential

requisites of EEC directive 89/392. They are factory tested

and on site installation is limited to water and electrical

connections.

STRUCTURE

Panels and bed plate are made from 

cataphoretic coat-

ed galvanised steel

to ensure total resistance to atmos-

pheric agents.

COMPRESSORS

Hermetic 

rotary scroll

compressor with sump heater

and thermal cut-out.

EVAPORATOR

AISI 316 stainless steel plate-type evaporator complete

with differential pressure switch.

Casing lined with

anti-condensate closed cell neoprene cladding.

CONDENSING COILS 

With copper tubes and high surface area aluminium fins.

Coil protection grilles as standard (HRAT E models).

FANS

External impeller axial-flow fans. Six-pole electric motor

with built-in thermal cut-out.

Housed in aerodynamic draught tubes with accident pre-

vention grill.

Device for operation in low external air

temperatures with pressure transducer for contin-

uous regulation of fan rotation speed.

REFRIGERANT CIRCUIT

The refrigerant circuit includes the following components:

filter, fluid passage indicator, thermostatic expansion valve

with external equaliser. Safety pressure switches to control

delivery and intake pressures. Unit complete with non-

freezing oil and R22 (HRAT-HRAN) or R407c refrigerant

(HRAT E).

Factory tested.

POWER AND CONTROL ELECTRICAL PANEL

Power and control electrical panel constructed in accor-

dance with IEC 204-1/EN60204-1, complete with compres-

sor contactor and thermal solenoid switch and 

door lock

safety device. Control via “HSW3” control panel.

OPTIONAL ACCESSORIES

- Removable metal mesh filter.

- Pump kit

- Inertial storage kit with pump, safety valve, filling assem-

bly, air vent valve, expansion tank, pressure gauge and

drain valve.

- Storage tank connection pipes.

- Rubber vibration dampers.

- Condensate collection pan kit.

- Remote keyboard kit.

- Serial interface kit.

- Protection grille kit (HRAT-HRAN models).

The above accessories are optional. Consult the relative

documentation for assembly instructions and technical

data.

8

7

4

5

2

1

3

6

10 

11 

1

Electrical panel

2

Control panel.

3

Plate heat exchanger

4

Low pressure switch

5

High pressure switch

6

Flow indicator

7

Scroll compressor

8

Dewatering filter

9

Thermostatic valve

10

Axial-flow fan

11

Finned coil

A

I

Summary of Contents for HRAN 0011

Page 1: ...3 Description of standard unit 4 Dimensioned drawings 5 Installation 6 Hydraulic connections 6 Electrical connections 8 General technical data 17 Cooling performance HRAT HRAT E 19 Cooling performance...

Page 2: ...use of electricity and water a number of fundamental safety rules must be observed namely The unit must not be used by children or by unfit persons without suitable supervision Do not touch the unit w...

Page 3: ...te spacing the forks as wide apart as possible If a crane is used pass the cables through the bottom of the bed plate making sure they do not exert pressure on the unit Once the packaging has been rem...

Page 4: ...ressure transducer for contin uous regulation of fan rotation speed REFRIGERANT CIRCUIT The refrigerant circuit includes the following components filter fluid passage indicator thermostatic expansion...

Page 5: ...77 Dimension 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151 Functional distances 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121 0151 L 900 900 900 900 900 900 900 900 900 900 900...

Page 6: ...tie rods if necessary If a heat pump unit is being installed fit a condensate col lection pan available as accessory The choice and installation of components is the responsi bility of the installer w...

Page 7: ...and 2 bars It is recommended that this operation be repeat ed after the unit has been operating for a number of hours The pressure of the installation should be checked regularly and if it drops below...

Page 8: ...ckable An efficient earth connection is obligatory Failure to earth the appliance absolves the manufac turer of all liability for damage In the case of three phase units ensure the phases are connecte...

Page 9: ...16 0 73 2 13 4 45 2 66 5 53 1A 1A 1A 1A 6 3A 0025 400 3N 50 2 25 4 09 38 5 0 16 0 73 2 41 4 82 3 13 6 43 1A 1A 1A 1 6A 6 3A 0031 400 3N 50 2 6 4 6 43 5 0 32 1 46 2 92 6 06 3 76 8 08 1A 1A 2A 1 6A 6 3...

Page 10: ...on fuse FU4 Water pump protection fuse KA1 High pressure switch relay KA2 Water pump control relay QM1 Compressor thermal overload switch KM1 Compressor contactor ELECTRICAL PANEL LAYOUT HRAT HRAN 001...

Page 11: ...een terminals 10 and 11 Connect the phase to termi nal 11 and the alarm warning device between terminal 10 and neutral max load 500mA at 24V It is prohibited to earth the secondary of the 24V transfor...

Page 12: ...Z1 1 C1 QM1 QS1 U N 45 46 47 WIRING DIAGRAM 0011 0021 SINGLE PHASE Factory installed components A1 Radio interference suppresser A2 Electronic controller A6 Unit control display keyboard BP3 Condensin...

Page 13: ...L N 1 1 M 2 3 C S R KM1 Z1 1 C1 QM1 QS1 U N 45 46 47 WIRING DIAGRAM 0025 0031 SINGLE PHASE Factory installed components A1 Radio interference suppresser A2 Electronic controller A6 Unit control displ...

Page 14: ...X 42 41 FU3 2 2 3 4 0 3 3 0 2 45 46 47 WIRING DIAGRAM 0011 0021THREE PHASE Factory installed components A1 Radio interference suppresser A2 Electronic controller A6 Unit control display keyboard BP3 C...

Page 15: ...RMINAL BOX 42 41 FU3 C3 2 2 3 5 0 3 3 4 0 3 3 0 2 45 46 47 WIRING DIAGRAM 0025 0061THREE PHASE Factory installed components A1 Radio interference suppresser A2 Electronic controller A6 Unit control di...

Page 16: ...0 38 41 42 45 46 47 30 31 33 15 43 30 42 20 0 MORSETTI PER INSTALLATORE INSTALLATOR TERMINAL BOX 17 42 41 WIRING DIAGRAM 00271 0151THREE PHASE Factory installed components A Radio interference suppres...

Page 17: ...city 1 kW 4 7 6 1 7 0 8 2 10 5 12 5 15 0 19 1 22 2 26 8 32 4 38 8 Compressor power input 1 kW 1 65 2 11 2 5 2 94 3 43 4 21 4 88 6 31 7 77 8 93 10 93 13 4 Total power input 1 kW 1 81 2 27 2 66 3 26 3 7...

Page 18: ...Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Number of compressors N 1 1 1 1 1 1 1 1 1 1 1 Number of circuits N 1 1 1 1 1 1 1 1 1 1 1 Power steps N 1 1 1 1 1 1 1 1 1 1 1 Hydr...

Page 19: ...1 1 1 1 1 1 1 2 1 2 1 2 Pev 27 7 29 4 31 1 32 9 34 8 36 7 Pf 6 0 6 2 6 3 6 5 6 7 6 9 Pa 2 7 2 7 2 8 2 8 2 8 2 8 43 Pat 2 9 2 9 2 9 2 9 3 0 3 0 Qev 1 0 1 1 1 1 1 1 1 2 1 2 Pev 25 6 27 2 28 9 30 6 32 3...

Page 20: ...0 9 1 9 2 9 2 Qev 3 4 3 5 3 6 3 7 3 8 3 9 Pev 18 6 19 7 20 9 22 2 23 4 24 8 Pf 19 1 19 6 20 2 20 8 21 4 22 0 Pa 8 8 8 9 8 9 9 0 9 1 9 1 43 Pat 9 5 9 5 9 6 9 7 9 7 9 8 Qev 3 3 3 4 3 5 3 6 3 7 3 8 Pev...

Page 21: ...6 1 7 1 7 1 8 1 8 1 9 Pev 18 4 19 5 20 7 22 0 23 2 24 6 Pf 8 8 9 1 9 4 9 7 9 9 10 2 Pa 3 5 3 5 3 5 3 6 3 6 3 6 40 Pat 3 8 3 8 3 9 3 9 3 9 4 0 Qev 1 5 1 6 1 6 1 7 1 7 1 8 Pev 16 2 17 2 18 3 19 4 20 5 2...

Page 22: ...4 2 5 2 6 2 7 2 7 2 8 Pev 22 9 24 3 25 7 27 0 28 4 29 8 Pf 13 9 14 3 14 7 15 1 15 5 15 8 Pa 4 6 4 7 4 7 4 8 4 8 4 8 32 Pat 5 0 5 0 5 0 5 1 5 1 5 1 Qev 2 4 2 5 2 5 2 6 2 7 2 7 Pev 22 0 23 3 24 7 26 0 2...

Page 23: ...input kW Pc evaporator pressure drop kPa Tw evaporator water outlet temperature C Pat total power input kW Pt Heating capacity kW Qc condenser water flow m3 h conditions out of the operating limits U...

Page 24: ...Pat 4 4 4 8 5 3 5 9 Qc 3 1 3 1 3 1 3 1 Pc 36 5 36 3 36 1 35 9 Pt 20 2 20 0 19 8 19 7 Pa 4 2 4 6 5 1 5 7 15 Pat 4 5 4 9 5 4 6 0 Qc 3 5 3 5 3 5 3 4 Pc 47 0 46 4 45 8 45 1 Pt 15 5 15 6 15 7 Pa 4 8 5 4 6...

Page 25: ...7 34 0031 55 46 40 37 34 0041 58 49 43 40 37 0051 58 49 43 40 37 0061 58 49 43 40 37 0071 65 56 50 47 44 0091 65 56 50 47 44 0101 65 57 52 49 46 0121 65 57 52 49 46 0151 65 57 52 49 46 Octave band Hz...

Page 26: ...pump HPA75H1 5 Storage tank pump HPA150H1 Model Water flow m3 h 0 6 0 8 1 00 1 2 1 4 1 6 1 8 l sec 0 167 0 222 0 278 0 333 0 389 0 444 0 500 Model Water flow m3 h 1 4 1 8 2 2 2 6 3 0 3 4 3 8 4 2 l se...

Page 27: ...1 plate heat exchanger 2 water differential pressure switch 3 compressor 4 fan 5 finned coil 6 liquid receiver 7 cycle reverse valve 8 thermostatic valve 9 liquid indicator 10 filter 11 check valve 1...

Page 28: ...ime with standard settings Set point values may be modified only after testing has been completed Before start ing up power up the unit for at least two hours by positioning QF1 and QS1 to ON and sett...

Page 29: ...Make sure the voltage falls within the limits speci fied and that the unbalance between the three phas es three phase power supply is no more than 3 ACTIVATING AND DEACTIVATINGTHE UNIT Place the remo...

Page 30: ...seconds The water return temperature is displayed the settings are complete To display the status of the unit the alarms and the operating hours return to the SEt level and then per form the procedur...

Reviews: