The keyboard of the CVM 20 electronic control unit is represented in FIG. 1  on the last page of this manual. 

1) PROCEDURE FOR SWITCHING ON AND OFF

SWITCHING ON THE UNIT

ATTENTION:  make sure that the unit has been live tor at least 8 hours before switching it on 

(to heat the oil in the compressor casing and separate any coolant present) 

• POWER LED (A)  on

• REMOTE OFF LED (C) off

• press key 1 - LED on

A TTENTION :  a lamp-test is performed automatically when the unit is switched on. 

SWITCHING ON SINGLE COMPRESSOR 

• press the key of the compressor to be switched on (Cl-C2) - SEL LED on

ATTENTION: 

-

the compressor may  delay starting due to: 

• timers set via the parameters

• no demand trom the thermoregulator

• presence of an alarm

SWITCHING  OFF SINGLE COMPRESSOR 

• press the key of the compressor to be switched off 

(CI-C2) 

- SEL LED off

ATTENTION:  only use this 

function in 

an emergency 

(stopping 

with 

no pump-down could

cause damage to the compressor that is 

not 

covered by 

guarantee)

SWITCHING OFF THE UNIT 

• press key 1  -

SEL 

LED off

2) COMPRESSOR OPERATION CONTROL

STATUS LED

SEL 

off and 

ON 

off= compressor not selected

SEL 

on and 

ON 

off= compressor selected,  but delayed

SEL 

on and 

ON 

on = compressor operating

SEL 

flashing and 

ON 

off = compressor in alarm mode

3) TEMPERATURE READINGS

EVAPORATOR INLET TEMPERATURE READINGS

• press key 

- IN LED on

• read the value on the display

EVAPORATOR 

OUTLET TEMPERATURE 

READINGS 

• press key 

- OUT LED on

• read the value on the display