4) REGULATION

CHILLED WATER REGULATION 

• press key 3 - LED on

CE MANUAL 

C 0206101 

• preset "set point" value appears on the display

• set the new "set point" value with key 6 to increase and key 7 to decrease

• press key 3 - LED off

The table below gives,  according to the number of steps, the "set point" and proportional band values 

normally in use. The theoretic minimum and maximum values, for the outlet temperature, indicated in 

the table refer to operation with nomina! flow rates and, therefore, with a thermal head at the evaporator 

of 5

°

C: 

N

° 

ofSteps 

Set Point  (

°

C) 

Proportional band 

(

°

C) 

min. T 

(

°

C)

max. 

(

°

C)

Theoretic outlet 

Theoretic outlet 

11 

12 

9.5 

2.5 

5.7 

10.8 

3

.,

5.6 

9.4 

5.7 

8.3 

A TTENTION : 

regulation is made according to the temperature reading at the evaporator in/et. 

ATTENTION 

if key 2 is used without the consent of Climaveneta or an Authorised Service 

Centre, the guarantee shall become 

null 

and void.

5) ALARMS

There are two types of alarm: circuit/ compressor alarms and unit alarms.

CIRCUIT/ COMPRESSOR ALARMS

Circuit/ compressor alarms are signalled by the SEL LED flashing and the B LED switching on.

UNIT ALARMS

Unit alarms are signalled by the B LED switching on.

To know the type of circuit /compressor or unit alarm:

• press key 5 - LED on: the alarm code appears on the display

To reset the circuit and compressor alarm:

• press the key of the relevant compressor 

(Cl-C2)

To reset the unit alarm:

• press key 5 - LED off, press key 1

ATTENTION 

if manual 

alarms are reset without the consent of Climaveneta or 

an 

Authorised

Service Centre the guarantee 

shall 

become 

null 

and void.

� CLIMAVENETA

-.. 