AWR MTD - AWR MTD/B
GB 01/2009
0025-0061
100
85
D
B
SYSTEM FILL G1/2
WATER OUTLET
A = C
524
559
UNIT VENT
SAFETY VALVE DISCHARGE
WATER INLET
0011
D
A
1 0 0
3 2 8
B
WATER INLET
WATER OUTLET
OPENING FOR CONDENSATE DRAIN CONNECTION
SYSTEM FILL G1/2
CONDENSATE DRAIN POSITION 0011-0061
C
524
559
SAFETY VALVE DISCHARGE
UNIT VENT
Dimensions
0011
0025
0031
0041
0051
0061
A
mm 61,5
61,5
61,5
61,5
61,5
61,5
B
mm
321,5
621,5
621,5
621,5
721,5
721,5
C
mm
91,5
61,5
61,5
61,5
61,5
61,5
D
mm
72,5
454,5
454,5
454,5
549,5
549,5
Water in/out fittings
Ø
1"-3/4"
1"-1"1/4
1"1/4
1"1/4
1"1/4
1"1/4
The heat pumps
must be fitted with a filling/top-up sys-
tem connected to the return line and a drain valve in the
lowest part of the system.
Systems containing antifreez
e or covered by specific
legislation must be fitted with low-loss headers.
The manufacturer is not liable for obstruction, breakage
or noise resulting from the
failure to install filters
or
vibration dampers.
Particular types of
water used for filling or topping up
must be treated with appropriate treatment systems.
For reference values, see the table.
CONDENSATE DRAIN
The unit is fitted with condensate pan; this must be connect-
ed to a drain system to take away the water that forms, see
the drawing.
If the outside air temperature is less than 0°C, the conden-
sate drained from the collection pan may freeze.
The unit must be supported on a suitable structure or brack-
ets to keep it off the ground, with a frost protection heater fit-
ted on the drain line.
PH
6-8
Electrical conductivity
less than 200 mV/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 50 ppm
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm