43
GB 01/2009
AWR MTD - AWR MTD/B
For parameter CF00, the value displayed will be 2.
To change the value of the parameter, press the up or down
button.
When having selected the value, press the set button. **
To exit the display and return to the previous level, press
esc.
**NOTE: pressing the set button confirms the new value;
pressing the esc button returns to the previous level without
changing the existing value.
Example of displaying and resetting (tens) the operating
hours for Pump 2.
From the main display, press the set button.
The display will show label Ai. Scroll the labels using the up
and down buttons until reaching label Hr.
DISPLAYING AND RESETTING COMPRESSOR/PUMP HOURS
Press the set button to display the first label, in this case the
operating hours for compressor 1 (CP01).
Scroll using the UP and DOWN buttons until displaying (if
featured among the resources) the operating hours for com-
pressor 2 (CP02) and the operating hours for the pumps
(PU01, PU02).
Press the set button to display the operating hours for pump
PU02.
The tens of operating hours are 2.
(The hours are expressed in tens: 2 indicates 20 operating
hours).
To reset the operating hours for pump PU02, press and hold
[set].
Note: to reset the operating hours for the other resources,
repeat the procedure described.
To exit the menu, press esc until returning to the main display.