8
AW HT
GB 05/2009
The heat pumps
must be fitted with a filling/top-up sys-
tem connected to the return line and a drain valve in the
lowest part of the system.
Systems containing antifreeze
or covered by specific
legislation must be fitted with low-loss headers.
The manufacturer is not liable for obstruction, breakage
or noise resulting from the f
ailure to install filters
or
vibration dampers.
Particular types of
water used for filling or topping up
must be treated with appropriate treatment systems.
For reference values, see the table.
CONDENSATE DRAIN
The unit is fitted with condensate pan; this must be connect-
ed to a drain system to take away the water that forms, see
the drawing.
If the outside air temperature is less than 0°C, the conden-
sate may gradually freeze.
The unit must be supported on a suitable structure or brack-
ets to keep it off the ground, with a frost protection heater fit-
ted on the drain line.
PH
6-8
Electrical conductivity
less than 200 mV/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0,3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 50 ppm
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm
CONDENSATE DRAIN POSITION 0031÷0061
OPENING FOR
CONDENSATE DRAIN
CONNECTION
B
A
Outlet G1 –1/4 male
Safety valve discharge
G1/2 female
Fill tap G1/2 female
Inlet G1 –1/4 male
Unit drain valve G1/2 female
Electrical connections
90
70
OUTLET
G1 –1/4 MALE
INLET
G1 –1/4
MALE
A
B
FILL TAP G1-1/4 FEMALE
SAFETY VALVE DISCHARGE
9 0 . 5
Dimensions
0031
0041
0061
0071
A
mm 210
322
322
452
B
mm
975
1000
1000
1183
Water connections M in/out
Ø
1"1/4
1"1/4
1"1/4
1”1/4
0031÷0061
0071