15
GB 05/2009
AW HT
• The room unit must be located around 1.5 metres from the floor, in a part of the room where the sensor can measure the room
temperature as precisely as possible; it must be sheltered from streams of cold air, sunlight or other sources of heat.
• If mounted on the wall, at the top of the room unit there must be enough space for assembly and removal when necessary.
The room unit, once removed from its base, is no longer powered and consequently is not working.
Installation procedure:
1. Press the plastic hooks, right and left, on the
support.
2. Remove the top part of the support
3. Fasten the support to the wall
4. Make the electrical connections, see the
wiring diagram, and attach the top part of the
support
5. Attach the room unit to the support.
Electrical connection
Room unit dimensions and support drilling template for installation.
1
2
3
CL+
CL-
G+
Terminal block
Room unit
Terminal block
Controller A1
42
18
5
10
0
82
4,2
9
56
60
10
0
80
11
39
67
Technical specifications
Room temperature measurement
Interface
Index of protection and safety class
Climate conditions
Weight
Power supply
Measurement
According to EN 12098:
Range 15 to 25 °C
Range 0 to 15 °C or 25 to 50 °C
Resolution
Maximum cable length
Case index of protection to EN 60 529
Safety class to EN 60 730
Degree of pollution EN 60 730
CE electromagnetic
compatibility conformity
- Immunity
- Emissions
Low voltage
- Electrical safety
Storage IEC721-3-1 class 1K3
Transport IEC721-3-2 class 2K3
Operation IEC721-3-3 class 3K5
Weight (excluding packaging)
Bus
0...50 °C
0.8 K tolerance
1.0 K tolerance
1/10 K
200m
IP20 for QAA7 …/ QAA55 …
Class 2 low-voltage if correctly installed
Normal pollution
89/336/EEC+2004/108/EEC and subsequent amend-
ments
- EN 61000-6-2
- EN 61000-6-3
2006/95/EEC and subsequent amendments
- EN 60730-1, EN 50090-2-2
temperature -20 to 65 °C
temperature -20 to 75 °C
temperature 0 to 50 °C (non-condensing)
170 g