Trilogy
®
Variable (VE) Series IOM - 60Hz HFC-410A
C r e a t e d : 4 O c t o b e r, 2 0 1 9
Refrigerant Circuit Diagram
Code
Fault
Mode
Possible Cause
Solution
69
Low Voltage Shutdown -
Inverter
ALL
Low input voltage
Check input voltage
ALL
Incorrect compressor wiring
Check wiring from drive to compressor
ALL
Incorrect wiring between CN2
and MIM
Check wiring from drive to MIM
ALL
Damaged Inverter board
If DC bus voltage stays below 200V, replace drive board.
***WARNING - Inverter board capacitors maintain high voltage for up to 15
minutes before fully discharging.
70
Power Supply Sync Warning
ALL
Bad Input Voltage
Check input voltage
71
Converter Over Current
Shutdown
ALL
Low Input Voltage
Check input voltage
72
Protect Operation -
Compressor Current
ALL
Internal draging of compressor
Check compressor and if all looks normal and problem is still present,
replace compressor
ALL
High compressor load
Reduce maximum operating speed of the system
ALL
Incorrect Inverter Board
Check board to ensure it is the correct size
ALL
Damaged Inverter board
If DC bus voltage stays below 200V, replace drive board.
***WARNING - Inverter board capacitors maintain high voltage for up to 15
minutes before fully discharging.
73
Protect Operation - Heat Sink
Temp.
ALL
Improper inverter contact with
heat sink
Check heat sink contact with inverter board
***WARNING - Inverter board capacitors maintain high voltage for up to 15
minutes before fully discharging.
74
Protect Operation -
Input Current
ALL
Low input voltage
Check input voltage
ALL
High compressor load
Reduce maximum operating speed of the system
CL
Water temp at range limit
Decrease loop temp
CL
Water temp at range limit
Decrease pump DT
HT
Air temp at range limit
Decrease intering air temp
HT
Air temp at range limit
Increase airfl ow setpoint
75
Lack of MIM Communications
ALL
Faulty control cable
Check continuity on harness between EXM and MIM
ALL
Damaged MIM
Replace MIM
ALL
Damaged EXM
Replace EXM
76
Low Voltage Shutdown
ALL
Under voltage
Check power supply and 24Vac before and during operation
ALL
Check power supply wires
ALL
Check 24Vac transformer tap for correct power supply voltage
77
Low Leaving Air temp
ALL
Low EAT
Bring EAT into range
ALL
Check unit capacity
Run mode to check unit capacity
ALL
Bad thermistor
Check temp vs. resistance curve per calculator
ALL
Incorrect airfl ow
Check airfl ow and reduce if nessesary.
ALL
Improperly installed airfl ow
sensor
Check installation
Troubleshooting