G e o t h e r m a l H e a t i n g a n d C o o l i n g
Trilogy
®
Variable
(VE) Series IOM - 60Hz HFC-410A
C r e a t e d : 4 O c t o b e r, 2 0 1 9
System Configuration
Navigating The Menus
The iGate
™
Connect thermostat has an easy–to–read color
screen that displays all the information you need to configure
the thermostat. Use the navigation buttons on the right
to quickly change the temperature, access features, and
configure settings.
Using the Navigation Buttons
The navigation buttons located on the right of the iGate
™
Connect thermostat let you select options and control the
iGate
™
Connect thermostat.
• ▲ (up)
On the Home screen, press ▲ to increase the
temperature set point by 1°F (0.5°C). For menus, press
▲ to move up.
• ▼ (down)
On the Home screen, press ▼ to decrease
the temperature set point by 1°F (0.5°C). For menus,
press ▼ to move down.
• ◀
(left)
On the Home screen, if Auto mode is enabled,
press
◀
to switch between heat and cool set points. For
menus, press
◀
to go back to the previous screen.
• ▶
(right)
On the Home screen, if Auto mode is enabled,
press
▶
to switch between heat and cool set points.
For menus, press
▶
to choose the currently highlighted
option.
• OK
On a menu screen, press
OK
to choose the
currently highlighted option. If a configuration option is
selected, pressing
OK
will keep its new value and return
back to the previous screen.
• MENU
Pressing
MENU
displays a list of all available
options. If a menu is currently displayed, pressing
MENU
will cancel any unsaved changes and return to the Home
screen.
• BACK
On a menu screen, press
BACK
to go back to
the previous screen.
On–Screen Keyboard
If you need to type in any information, an on–screen
keyboard will appear. To enter a letter or number, move to the
character by pressing the arrow keys and then press OK to
select it.
Select
to enter capital letters; select
to enter
commonly used symbols. If you make a mistake, press to
delete the text .
To keep your changes, select
. To cancel your changes,
press BACK.
Configuring The iGate
™
Connect Thermostat
The first step after installing the iGate
™
Connect thermostat
is to configure the settings for the various devices (such as
a furnace or air conditioner) that are being connected. An
access code is required to enter the Installation Settings
menu from the iGate Connect thermostat. The access code
is 4795. It must be entered using the arrow keys on the
thermostat to select each number and the OK button to enter
each one.
Thermostat Config
To configure the iGate
™
Connect thermostat:
1. From the Home screen,
press MENU.
2. Select Settings
▶
Installation.
3. Select Thermostat Config
Aux Heat Option
Configures the thermostat for electric
auxiliary heat or no auxiliary heat (none).
Equipment
To configure equipment on the iGate
™
Connect thermostat:
1. From the Home screen,
press MENU.
2. Select Settings
▶
Installation.
3. Select Equipment.
Capacity Configuration
Min Heating Capacity
Configures the minimum unit heating
capacity. When the space requires a heating capacity below
this setting the unit will cycle off. Range will depend on unit
model.
Max Heating Capacity
Configures the maximum unit
heating capacity. When the space requires a heating
capacity above this setting the unit will call for auxiliary heat
(if applicable). Range will depend on unit model.
Min Cooling Capacity
Configures the minimum unit cooling
capacity. When the space requires a cooling capacity below
this setting the unit will cycle off. Range will depend on unit
model.
Max Cooling Capacity
Configures the maximum operational
unit cooling capacity. Range will depend on unit model.
Unit Configuration
The Unit Configuration settings allow the installing technician
to configure the thermostat to the installed equipment.
NOTE:
Unit Config is only necessary when replacing an EXM
controller. The Unit Config settings are programmed at the
factory when the unit is built.
Heat Pump Family
Select the family of heat pump installed.
Heat Pump Size
Select the unit model (0930, 1545, 1860,
or 2472).
Blower Type
Select the blower type (None or ECM).
Loop Config
Selects the type of internal flow device. None,
VS Pump – variable speed internal pump, or MOD Valve –
internal modulating water control valve.
Loop Pump (or Valve) Config
Configures the internal vFlow device to the application.
Loop Option (if applicable)
Configures the internal variable
speed pump to operate in a Single system (one unit, one