Electrical - Line Voltage
�
WARNING!
�
�
CAUTION!
�
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Electrical - Line Voltage
All field installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for field connections that
must be made by the installing (or electrical) contractor.
All final electrical connections must be made with a length of
flexible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
�
WARNING!
�
�
CAUTION!
�
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Unit Power Supply
(see electrical tables 7a - 7b for minimum circuit amps and
maximum breaker size)
VE
Model Rated Voltage
Compressor
Ext
Loop
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
RLA LRA
0930
208/230/60/1
20.0 20.0
1.4
2.6
24.0
29.0
45
1860
208/230/60/1
28.0 28.0
1.4
6.9
36.3
43.3
70
Rated Voltage of 208-230/60/1
Min/Max Voltage of 197/254
HACR circuit breaker in USA only
All fuses Class RK-5
Table 7: Trilogy
®
(VE) Series ECM with Internal Flow
Controller Electrical Data
WARNING!
Disconnect electrical power source to
prevent injury or death from electrical shock. The
capacitors on the inverter board store electrical energy.
They will remain charged long after power has been
disconnected. Extreme care should be used when
working around these capacitors.
Figure 19: Trilogy Single Phase Line Voltage
Field Wiring
Power Connection
Line voltage connection is made by connecting the incoming
line voltage wires to the terminal block as shown in Figure 19.
Consult Table 7 for correct fuse size. Note: always refer to the
unit dataplate for unit electrical data.
208 Volt Operation
All residential 208-230 Volt units are factory wired for 230
Volt operation. The transformer may be switched to the
208V tap as illustrated on the wiring diagram by switching
the orange wire from the contactor terminal to the 208v
transformer tap.