Table 4: TRC Electrical Data (60Hz)
Standard Unit
With Secondary Pump
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY
RLA
LRA
TRC09
A
115/60/1
104-126
1
8.0
46.5
0.5
8.5
10.5
20
8.8
11.3
20
G
208-230/60/1
197-254
1
4.5
23.0
0.4
4.9
6.0
15
5.3
6.4
15
E
265/60/1
239-292
1
5.0
19.0
0.4
5.4
6.7
15
6.2
7.5
15
TRC12
A
115/60/1
104-126
1
9.5
50.0
0.5
10.0
12.4
20
11.5
13.8
20
G
208-230/60/1
197-254
1
4.7
25.0
0.6
5.3
6.5
15
5.7
7.3
15
E
265/60/1
239-292
1
4.2
22.0
0.4
4.6
5.7
15
5.4
6.5
15
TRC15
G
208-230/60/1
197-254
1
5.6
30.0
0.8
6.4
7.8
15
7.2
8.6
15
E
265/60/1
239-292
1
4.7
28.5
0.6
5.3
6.5
15
6.2
7.3
15
TRC18
G
208-230/60/1
197-254
1
6.8
38.0
0.7
7.5
9.2
15
8.3
10.0
15
E
265/60/1
239-292
1
6.2
29.0
0.6
6.8
8.4
15
7.6
9.2
15
Table 5: TRC Electrical Data (50Hz)
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY
RLA
LRA
TRC09
V
220-240/50/1
198-264
1
3.2
17
0.4
3.6
4.4
15.0
TRC12
V
220-240/50/1
198-264
1
4.0
19
0.4
4.4
5.4
15.0
TRC15
V
220-240/50/1
198-264
1
4.7
23
0.6
5.3
6.5
15.0
TRC18
V
220-240/50/1
198-264
1
5.6
25
0.6
6.2
7.6