Tranquility
®
D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e
R e v. : 1 0 M a r c h , 2 0 1 5
42
G e o t h e r m a l H e a t i n g a n d C o o l i n g
ON
OFF
ON
OFF
1
2
3
4
P1
L1
L2
L3
L4
P2
197 -
254 V
Turning Breaker on in Panel or Auxiliary Heat Control
B-C
Static Pressure Check
B-D
Return
Air
Supply
Air
Static Pressure Probe
inserted into 1/2” Hole
-.18 + .21
With the blower at full load air speed,
take a reading from the Digital
Manameter. Check the reading against
the IOM blower tables or in the tables
shown below to determine the maximum
external static pressure.
Verify that all grilles and registers are
open and free.
Use a Magnetic Static Pressure Tip tool
(far right) to check the static pressure.
Add both together to get Total Static
Example: .39 Static Pressure
Tranquility
®
22 (TZ) Series
Airflow in CFM with wet coil and clean air filter
Model Max ESP
(in. wg)
024
0.75
030
0.5
036
0.6
042
0.6
048
0.75
060
0.75
Airflow is controlled within 5% up to the Max ESP
shown with wet coil.
Factory shipped on default CFM.
Tranquility
®
30 (TE) Series
Airflow in CFM with wet coil and clean air filter
Model
Max
ESP
(in. wg)
026
1.0
038
0.9
049
1.0
064
0.7
072
0.7
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
ECM Blower Performance Static Pressure Tables
Magnetic Static
Pressure Tip
Tranquility
®
Digital
Air Handler (TAH)
Model Max ESP
(in. wg)
026
1.0
038
0.9
049
1.0
064
0.7