BACnet, Modbus, N2 Points List, Cont’d.
Note 1: Indicates Physical Inputs/Outputs to/from Master Controller.
Note 2: Indicates Recommended Status Indication of important parameters.
Note 3: Indicates Command Inputs from Bacview/BAS system.
Note 4: Indicates Customer Alarm Reset Functions from Bacview/BAS System.
Note 5: Indicates all System Alarms possible.
Table Continued on Next Page
Name
Note
BACnet MSTP
Modbus
N2
Object Name
Value
Type Object
ID
Exp:
Num
I/O Type
Device ID Read
Only
Object
Type
Register
Type
ID
C1 Suction Superheat
2
c1_suc_superheat_1
31.6 °F
BAV AV:142
DEV:2460xx
Heat Low Suction Press Alm
Sp 410a
mod_heat_lo_suc_press_
sp_410_1
92.0
BAV AV:145
DEV:2460xx
float value
40367
data float
157
Load Water Out Temp Status
2
load_out_tmp_stat_1
42.2
BAV AV:146
DEV:2460xx
float value
40397
data float
172
Heat Mode Low Suction Alm
Temp
heat_lo_suct_tmp_1
32.0
BAV AV:147
DEV:2460xx
float value
40369
data float
158
Load Water Header Low Diff Alm
Pressure
2
lo_ld_diff_pr_1
1.5
BAV AV:148
DEV:2460xx
float value
40399
data float
173
Source Water Header Low Diff
Alm Pressure
2
lo_src_diff_pr_1
1.5
BAV AV:149
DEV:2460xx
float value
40401
data float
174
Cool Mode Low Suction Press
Alm Stp
mod_cool_low_press_sp_1
92.0
BAV AV:150
DEV:2460xx
float value
40429
data float
188
Heat Mode Low Suction Press
Alarm Stp
mod_heat_low_press_sp_1
92.0
BAV AV:152
DEV:2460xx
float value
40441
data float
194
Reset Alarm DELAY
reset_alm_delay_1
10.0
BAV AV:153
DEV:2460xx
float value
40497
data float
222
Source Wtr In Temp Status
2
source_in_tmp_stat_1
77.3
BAV AV:154
DEV:2460xx
float value
40505
data float
226
Source Wtr Out Temp Status
2
source_out_tmp_stat_1
105.5
BAV AV:156
DEV:2460xx
float value
40511
data float
229
Evap In Temp Status
evap_in_tmp_stat_1
77.3
BAV AV:157
DEV:2460xx
float value
40287
data float
112
Evap Wtr Outlet Temp Status
2
evap_out_temp_stat_1
41.9
BAV AV:158
DEV:2460xx
float value
40289
data float
114
Num of Stages ON
stages_on_1
0.0
BAV AV:185
DEV:2460xx
float value
40129
data float
37
Actual Low Diff Press Trip Load
2
act_lo_diff_press_ld_1
2.0 °F
BAV AV:186
DEV:2460xx
float value
40023
data float
1
Actual Low Diff Press Trip
Source
2
act_lo_diff_press_src_1
3.9 °F
BAV AV:187
DEV:2460xx
float value
40025
data float
2
C1 Comp Cycle Count
2
c1_comp_cyc_count_1
0.0
BAV AV:188
DEV:2460xx
float value
40071
data float
9
C2 Comp Cycle Count
2
c2_comp_cyc_count_1
0.0
BAV AV:189
DEV:2460xx
float value
40077
data float
10
Diff Pressure Trip Multiplier
diff_pr_trip_mult_1
0.6
BAV AV:190
DEV:2460xx
float value
40087
data float
15
Estimated Kw Per Ton
est_kw_per_ton_1
1.0896169 °F
BAV AV:191
DEV:2460xx
float value
40095
data float
19
Estimated Tons
est_tons_1
46.08453 °F
BAV AV:192
DEV:2460xx
float value
40097
data float
20
Estimated Watts
est_watts_1
50214.48 °F
BAV AV:193
DEV:2460xx
float value
40099
data float
22
Load Water Diff Pr Cali Point
ldpsi_cali_point_1
0.0
BAV AV:194
DEV:2460xx
float value
40101
data float
23
Max Delta Temp- Load
2
max_delta_temp_ld_1
10.0
BAV AV:195
DEV:2460xx
float value
40111
data float
28
Max Delta Temp- Source
2
max_delta_temp_src_1
10.0
BAV AV:196
DEV:2460xx
float value
40115
data float
29
Num 32.5 Ton Comps Req Stg1
num65t1req_1
0.0
BAV AV:197
DEV:2460xx
float value
40127
data float
35
C2 Saturated Suction Temp
c2_suc_sat_tmp_1
45.4
BAV AV:200
DEV:2460xx
float value
40137
data float
43
PID Differential Factor
2
pid_diff_fact_1
5.0
BAV AV:201
DEV:2460xx
float value
40131
data float
38
Source Water Diff Pr Cali Point
srcpsi_cali_point_1
0.0
BAV AV:202
DEV:2460xx
float value
40133
data float
39
Default HP Using High Head
Pressure
mod_defaulthp_usehihp_1
200.0
BAV AV:203
DEV:2460xx
float value
40081
data float
12
Default HP Using Low Head
Pressure
mod_defaulthp_uselowhp_1
350.0
BAV AV:204
DEV:2460xx
float value
40083
data float
13
C2 Suction Superheat
2
c2_suc_superheat_1
32.0 °F
BAV AV:447
DEV:2460xx
float value
40139
data float
44
Cool Mode Setpoint Offset
cool_stp_with_offset_1
44.0
BAV AV:581
DEV:2460xx
float value
40189
data float
67
Comp 1 Cycles
2
c1_cycles_1
0.0
BAV AV:583
DEV:2460xx
float value
40193
data float
69
Comp 1 Runtime
2
c1_runtime_1
2.215
BAV AV:584
DEV:2460xx
float value
40195
data float
70
Comp 2 Cycles
2
c2_cycles_1
0.0
BAV AV:585
DEV:2460xx
float value
40205
data float
71
Comp 2 Runtime
2
c2_runtime_1
2.1
BAV AV:586
DEV:2460xx
float value
40207
data float
72
Cool Mode Setpoint Offset
cool_stp_offset_1
0.0
BAV AV:588
DEV:2460xx
float value
40253
data float
101
Heating Setpoint Offset
heat_stp_offset_1
0.0
BAV AV:589
DEV:2460xx
float value
40255
data float
102
Heat Mode Setpoint Offset
heat_stp_with_offset_1
120.0
BAV AV:609
DEV:2460xx
float value
40387
data float
167
Max Cool Ramp Rate
max_cool_ramp_rate_1
10.0
BAV AV:615
DEV:2460xx
float value
40105
data float
25
Maximum Heat Ramp Rate
max_heat_ramp_rate_1
10.0
BAV AV:616
DEV:2460xx
float value
40117
data float
30
Num of Cooling Comp
Requested
2
clg_comp_req_1
0.0
BAV AV:627
DEV:2460xx
float value
40487
data float
217
Num of Heating Comp
Requested
2
htg_comp_req_1
0.0
BAV AV:628
DEV:2460xx
float value
40489
data float
218
Time Interval Before Compr
Runtime Refresh
runtime_refresh_1
84.0 hr
BAV AV:631
DEV:2460xx
float value
40499
data float
223
Source Mot Valve PID Out %
source_mv_pidout_1
4.8
BAV AV:633
DEV:2460xx
float value
40507
data float
227
Cool Mode PID Count
2
stg1_clg_pid_1
0.0
BAV AV:634
DEV:2460xx
float value
40317
data float
140
Heat Mode PID Count
2
stg1_htg_pid_1
0.0
BAV AV:635
DEV:2460xx
float value
40319
data float
141
Step PID Value for 65T
2
step_pid_65t_1
50.0
BAV AV:638
DEV:2460xx
float value
40135
data float
40
C1 Cycles Reset
4
c1_cycles_reset_1
Off
BBV
BV:1
DEV:2460xx
discrete out
1
binary out
7
System Run Command Status
run_1
On
BBV
BV:2
DEV:2460xx
discrete in
10023
binary in
21
C1 Hi Discharge Pressure
Unload
c1_hi_dis_psi_unld_1
Off
BBV
BV:3
DEV:2460xx
discrete in
10018
binary in
12
C1 Hi Discharge Temp Unload
c1_hi_dis_tmp_unld_1
Off
BBV
BV:4
DEV:2460xx
discrete in
10021
binary in
13
C1 Extra-Low Suction Pressure
Unload
c1_lolo_suc_psi_unld_1
Off
BBV
BV:5
DEV:2460xx
discrete in
10022
binary in
14
C1 Low Suction Pressure Unload
c1_lo_suc_psi_unld_1
Off
BBV
BV:6
DEV:2460xx
discrete in
10025
binary in
15
Alarm Status Output
2
alarm_bo_1
Off
BBV
BV:7
DEV:2460xx
discrete in
10004
binary in
2
Cool Mode Enable Input
cool_enable_1
On
BBV
BV:8
DEV:2460xx
discrete in
10016
binary in
10