Tranquility
®
Large Water-to-Water (TMW) Series
R e v. : O c t o b e r 5 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
BACnet, Modbus, N2 Points List
Name
Note
BACnet MSTP
Modbus
N2
Object Name
Value
Type Object
ID
Exp:
Num
I/O Type
Device ID Read
Only
Object
Type
Register
Type
ID
C1-C2 Status Inputs
1
c1-2_inputs_1
-60.2
BAI
AI:1
0:12
Thermistor
DEV:2460xx
float value
40001
analog in
1
C1 Discharge Pressure
1
c1_disch_pres_1
128.4
BAI
AI:2
0:03
0-5 Volt
DEV:2460xx
float value
40003
analog in
2
C1 Discharge Temp
1
c1_disch_temp_1
76.9 °F
BAI
AI:3
0:07
Thermistor
DEV:2460xx
float value
40005
analog in
3
C1 Suction Pressure
1
c1_suc_pres_1
130.6
BAI
AI:4
0:01
0-5 Volt
DEV:2460xx
float value
40007
analog in
4
C1 Suction Temp
1
c1_suct_temp_1
77.0 °F
BAI
AI:5
0:05
Thermistor
DEV:2460xx
float value
40009
analog in
5
C2 Discharge Pressure
1
c2_disch_pres_1
-3.7
BAI
AI:6
0:04
0-5 Volt
DEV:2460xx
float value
40011
analog in
6
C2 Discharge Temp
1
c2_disch_temp_1
77.3 °F
BAI
AI:7
0:08
Thermistor
DEV:2460xx
float value
40013
analog in
7
Load Inlet Temp Cool Mode
1
load_in_temp_cool_1
77.3 °F
BAI
AI:8
1:09
Thermistor
DEV:2460xx
float value
40027
analog in
14
C2 Suction Pressure
1
c2_suc_pres_1
130.6
BAI
AI:9
0:02
0-5 Volt
DEV:2460xx
float value
40015
analog in
8
C2 Suction Temp
1
c2_suct_temp_1
77.4 °F
BAI
AI:10
0:06
Thermistor
DEV:2460xx
float value
40017
analog in
9
Load Inlet Temp Heat Mode
1
load_in_temp_heat_1
77.3 °F
BAI
AI:11
1:09
Thermistor
DEV:2460xx
float value
40029
analog in
15
Load Outlet Temp Cool Mode
1
load_out_temp_cool_1
42.2 °F
BAI
AI:12
1:10
Thermistor
DEV:2460xx
float value
40031
analog in
16
Mot Valve Status Inputs
1
valve_in_1
99.2
BAI
AI:13
0:11
Thermistor
DEV:2460xx
float value
40047
analog in
24
Load Outlet Temp Heat Mode
1
load_out_temp_heat_1
42.2 °F
BAI
AI:14
1:10
Thermistor
DEV:2460xx
float value
40033
analog in
17
Diff Press Hi Range Load Flow
0-5VDC
1
diff_pr_hi_range_load_010_1
15.23
BAI
AI:15
1:14
0-5 Volt
DEV:2460xx
float value
40019
analog in
10
Diff Press Hi Range Source Flow
0-5VDC
1
diff_pr_hi_range_source_010_1
15.23
BAI
AI:16
1:13
0-5 Volt
DEV:2460xx
float value
40021
analog in
11
Diff Press Low Range Load Flow
0-5VDC
1
diff_pr_load_010_1
5.07
BAI
AI:17
1:14
0-5 Volt
DEV:2460xx
Diff Press Low Range Source
Flow 0-5VDC
1
diff_pr_source_010_1
5.07
BAI
AI:18
1:13
0-5 Volt
DEV:2460xx
Source Inlet Temp Cool Mode
1
src_in_temp_cool_1
77.3 °F
BAI
AI:19
1:11
Thermistor
DEV:2460xx
float value
40039
analog in
20
Source Inlet Temp Heat Mode
1
src_in_temp_heat_1
77.3 °F
BAI
AI:20
1:11
Thermistor
DEV:2460xx
float value
40041
analog in
21
Source Outlet Temp Cool Mode
1
src_out_temp_cool_1
105.5 °F
BAI
AI:21
1:12
Thermistor
DEV:2460xx
float value
40043
analog in
22
Source Outlet Temp Heat Mode
1
src_out_temp_heat_1
105.5 °F
BAI
AI:22
1:12
Thermistor
DEV:2460xx
float value
40045
analog in
23
Remote Cool Setpoint 0-10VDC
1
rem_chw_stp_010_1
7.7
BAI
AI:23
1:15
0-10 Volt
DEV:2460xx
float value
40035
analog in
18
Remote Heat Setpoint 0-10VDC
1
rem_cw_stp_010_1
7.8
BAI
AI:25
1:16
0-10 Volt
DEV:2460xx
float value
40037
analog in
19
Phase Input OK
1
phase_in_ok_1
On
BBI
BI:1
1:01
Binary Input
DEV:2460xx
discrete in
10008
binary in
6
Load Water Flow Switch
1
ld_water_flow_1
Off
BBI
BI:2
1:02
Universal Input
DEV:2460xx
discrete in
10007
binary in
5
Source Water Flow Switch
1
src_water_flow_1
Off
BBI
BI:3
1:03
Universal Input
DEV:2460xx
discrete in
10010
binary in
8
Digital Input Cool Enable
1
dig_cool_enable_1
Off
BBI
BI:4
1:04
Universal Input
DEV:2460xx
Digital Input Heat Enable
1
dig_heat_enable_1
Off
BBI
BI:5
1:05
Universal Input
DEV:2460xx
Reset All Alarms
1
reset_all_alrm_1
Off
BBI
BI:7
1:06
Universal Input
DEV:2460xx
discrete in
10009
binary in
7
Source Cond Mot Valve AO
1
cnd_vlv_ao_1
4.80%
BAO
AO:1
0:01
Electrical 0-10 Volt
DEV:2460xx
float value
40051
analog out 2
Alarm Flash Code AO
1
alm_flash_code_ao_1
0.00%
BAO
AO:2
0:02
Electrical 0-10 Volt
DEV:2460xx
float value
40049
analog out 1
Cool Reversing Valve S/S
1
cool_rev_vlv_bo_1
On
BBO
BO:1
0:03 Relay / Triac Output DEV:2460xx
discrete in
10014
binary out
5
Chiller Status
1
chlr_stat_1
On
BBO
BO:2
0:06 Relay / Triac Output DEV:2460xx
discrete in
10003
binary out
2
Comp 1 S/S
1
comp_1_ss_bo_1
Off
BBO
BO:3
0:01 Relay / Triac Output DEV:2460xx
discrete in
10012
binary out
3
Comp 2 S/S
1
comp_2_ss_bo_1
Off
BBO
BO:4
0:02 Relay / Triac Output DEV:2460xx
discrete in
10013
binary out
4
Load Mot Vlv S/S
1
load_vlv_ss_bo_1
On
BBO
BO:5
0:04 Relay / Triac Output DEV:2460xx
discrete in
10015
binary out
6
Alarm
1
o245_1
Off
BBO
BO:6
0:05 Relay / Triac Output DEV:2460xx
discrete in
10002
binary out
1
# Cool Comp Requested
2
cool_comp_req_1
0.0
BAV
AV:3
DEV:2460xx
float value
40059
data float
3
# Heat Comp Requested
2
heat_comp_req_1
0.0
BAV
AV:4
DEV:2460xx
float value
40061
data float
4
Active Cool Setpoint
2
cool_stp_stat_1
44.0 °F
BAV
AV:5
DEV:2460xx
float value
40063
data float
5
Active Heat Setpoint
2
heat_stp_stat_1
120.0 °F
BAV
AV:6
DEV:2460xx
float value
40065
data float
6
C1 Disch Pressure Status
2
c1_disch_pres_stat_1
128.4
BAV
AV:7
DEV:2460xx
float value
40069
data float
8
C1 Discharge Temp Status
2
c1_disch_temp_stat_1
76.9
BAV
AV:9
DEV:2460xx
float value
40093
data float
11
Cond Mot Valve PID I-gain
cdmv_i_gain_1
0.01
BAV
AV:14
DEV:2460xx
float value
40147
data float
48
C1 Suction Pressure Status
2
c1_suc_pres_stat_1
130.7
BAV
AV:16
DEV:2460xx
float value
40103
data float
14
C1 Suction Temp Status
2
c1_suct_temp_stat_1
77.0
BAV
AV:19
DEV:2460xx
float value
40107
data float
16
C2 Discharge Pressure Status
2
c2_disch_pres_stat_1
-3.9
BAV
AV:20
DEV:2460xx
float value
40109
data float
17
Cond Mot Valve PID Min Percent
cdmv_pid_mnpct_1
35.0
BAV
AV:22
DEV:2460xx
float value
40171
data float
50
Cond Mot Valve PID P-gain
cdmv_p_gain_1
2.0
BAV
AV:23
DEV:2460xx
float value
40175
data float
52
Cond In Temp Status
cond_in_tmp_stat_1
77.3 °F
BAV
AV:26
DEV:2460xx
float value
40211
data float
76
Cond Wtr Inlet Temp Status
2
cond_in_temp_stat_1
77.3
BAV
AV:29
DEV:2460xx
float value
40209
data float
74
Alarm Flash Code number
2
alarm_code_1
1.0
BAV
AV:31
DEV:2460xx
float value
40067
data float
7
Cool Mode PID Deadband1
clg_db1_1
1.0
BAV
AV:32
DEV:2460xx
float value
40073
data float
18
Cool Mode PID Fall Rate
clg_fall_1
40.0
BAV
AV:35
DEV:2460xx
float value
40079
data float
21
Cool Mode PID I-gain
clg_i_gain_1
0.8
BAV
AV:38
DEV:2460xx
float value
40085
data float
24
Cool Mode PID P-gain
clg_p_gain_1
16.0
BAV
AV:40
DEV:2460xx
float value
40089
data float
26
Cool Mode PID Rise Rate
clg_rise_1
10.0 sec
BAV
AV:41
DEV:2460xx
float value
40091
data float
27
Cond Wtr Outlet Temp Status
2
cond_out_temp_stat_1
105.5
BAV
AV:42
DEV:2460xx
float value
40213
data float
77
C2 Discharge Temp Status
2
c2_disch_temp_stat_1
77.3
BAV
AV:43
DEV:2460xx
float value
40113
data float
31
Cool Mode Evap Wtr Low Alm
Temp
cool_evap_lo_tmp_1
38.0
BAV
AV:44
DEV:2460xx
float value
40245
data float
97
Cool Mode Cond Wtr Hi Alm
Temp
cool_high_cond_tmp_1
140.0
BAV
AV:45
DEV:2460xx
float value
40249
data float
99
Cool Mode Evap Wtr Hi Alm
Temp
cool_hi_evap_tmp_1
90.0
BAV
AV:47
DEV:2460xx
float value
40251
data float
100
Note 1: Indicates Physical Inputs/Outputs to/from Master Controller.
Note 2: Indicates Recommended Status Indication of important parameters.
Note 3: Indicates Command Inputs from Bacview/BAS system.
Note 4: Indicates Customer Alarm Reset Functions from Bacview/BAS System.
Note 5: Indicates all System Alarms possible.
Table Continued on Next Page