ClimateMaster LCU Series Installation, Operation & Maintenance Instructions Manual Download Page 11

Page 11

MAINTENANCE

Maintenance Procedures

Perform the maintenance procedures outlined below
periodically as indicated:

To prevent injury or death due to electrical shock or
contact with moving parts, open unit disconnect
switch before servicing unit.

FILTERS: Inspect filters. Establish a regular mainte-
nance schedule. Replace/clean filter frequently depend-
ing upon need.

To remove the filter from a Large Commercial Unit, slide
the filter out of its frame located in the return air open-
ing. When re-installing the filter, use the slide-in rails of
the filter frame to guide the filter into the proper position.
Verify that the airflow arrow found on the top of each
filter points toward the unit. Always replace filters with
the same size and quantity of filters as removed from the
unit.

To avoid fouled machinery and extensive unit clean-
up, DO NOT operate units without filters in place.
DO NOT use equipment as a temporary heating or
cooling source during construction.

CONDENSATE PANS: Check condensate drain pans
for algae growth  every three (3) months. If algae growth
is apparent, consult a water treatment specialist for
proper chemical treatment. The application of an algae-
cide every three (3) months will typically eliminate algae
problems in most locations.

FAN MOTORS: Lubricate fan motors annually. All
ClimateMaster Large Commercial Units are fully
lubricated at the factory. DO NOT lubricate during
installation. Check all belts and sheaves for wear. Adjust
and replace as needed.

Conduct amperage checks annually. Amperage draw
should not exceed normal full load or rated load amps by
more than 10% of the values noted on the unit nameplate.
Maintain a log of amperage values to detect deterioration
prior to component failure.

UNIT INSPECTION: Visually inspect the unit annu-
ally. Pay special attention to hose assemblies. Repair any
leaks and replace deteriorated hoses immediately.

COMPRESSOR: Conduct amperage checks on the
compressor annually. Amperage draw should not exceed

normal full load or rated load amps by more than 10% of
the values noted on the unit nameplate. Maintain a log of
amperage values to detect deterioration prior to compo-
nent failure.

When replacing the compressor contactor or lockout
relay in a unit with electromechanical controls, use
only ClimateMaster replacement parts. Substitution
of other components may result in an inoperative
safety circuit and may cause a hazardous condition.

HEAT EXCHANGERS: Clean heat exchangers
annually. Inspect heat exchangers regularly and clean
more frequently if the unit is located in a “dirty” environ-
ment.

NOTE: If the unit must be reset more than twice,
check the unit for a dirty filter, abnormal entering
water temperature, inadequate or excessive water
flow and internal malfunction. If the unit continues to
cutout, contact a trained service technician.

Controller and Safety Protection

The microprocessor-based controller monitors and

controls unit operation. The controller provides
compressor sequencing, high and low pressure
monitoring, field selectable water and air coil freeze
protection sensing, condensate overflow sensing, over/
under voltage monitoring, and unit performance sentinel.
The control provides a test mode, short cycle protection,
random start-up, a fault LED, fault memory, and
intelligent fault retry. Note the controls operation below
and refer to the controller AOM provided with each unit
for specific controller features, specifications and
operations.

Interstage Time Delay  On two compressor units, a time
delay between stage I and stage 2 can be set with a dip
switch on compressor 2 controller.

Pressure Switches  Pressure switches are normally

c

losed during normal operating conditions, and open

upon fault. The high pressure switch opens at 375 PSIG
and automatically closes at 3 00 PSIG. The low pressure

s

witch opens at 10 PSIG and automatically closes at 33

PSIG. The low pressure switch must be open for 30
continuous seconds to cause a fault.

Freeze Protection  Thermistors used for freeze
protection, is a NTC (negative temperature coefficient)
type. Freeze protection is set at 30 degrees Fahrenheit for
water systems. If antifreeze is used, the freeze protection
can be set at 10 degrees Fahrenheit by cutting a jumper
on the controller.

WARNING

!

CAUTION

Summary of Contents for LCU Series

Page 1: ...Installation Operation Maintenance Instructions Large Commercial Series Water Source Heat Pumps LCU Series...

Page 2: ...Installation 3 Location and Access 4 Installation 4 Installation of Supply and Return Piping 4 Condensate Piping 5 Sound Attenuation for Large Commercial Units 6 Electrical Wiring 6 Wall Mounted Therm...

Page 3: ...after it is removed Inspection Upon receipt of shipment at the job site carefully check the shipment against the bill of lading Make sure all units have been received Inspect the carton or crating of...

Page 4: ...vicing of the compressor and coils without removal of the unit 3 Provide an unobstructed path to the unit within the closet or mechanical room to enable removal of the unit if necessary 4 Provide acce...

Page 5: ...to avoid condensate pan overflow at initial start up DO NOT bend or kink supply lines or hoses Optional pressure rated hose assemblies designed specifically for use with ClimateMaster units are availa...

Page 6: ...hock open the power supply disconnect switch and secure it in an open position during installation Use only copper conductors for field installed electrical wiring Unit terminals are not designed to a...

Page 7: ...nt of 40 F with entering air at 40 F entering water at 40 F and with both air and water at the stated flow rates of ARI Standard 320 96 rating test for initial winter start up Notes 1 These are not no...

Page 8: ...e to equal the rate of bleed 7 Refill the system and add trisodium phosphate in a proportion of approximately one pound per 150 gallons of water Reset the boiler to raise the loop temperature to about...

Page 9: ...ystem Water Temperature Ensure that it is within an acceptable range to facilitate start up When conducting this check also verify proper heating and cooling set points 3 System Water pH Verify system...

Page 10: ...e imme diately after checking cooling cycle operation A time delay will prevent the compressor from re starting for approximately 5 minutes NOTE Large Commercial heat pump units are UNIT START UP WARN...

Page 11: ...ore than 10 of the values noted on the unit nameplate Maintain a log of amperage values to detect deterioration prior to compo nent failure When replacing the compressor contactor or lockout relay in...

Page 12: ...d source the air coil Grounding the condensate overflow signal from the controller causes a fault after 30 continuous seconds Over Under Voltage When the controller senses a voltage over 30Vac or unde...

Reviews: