ClimateMaster LCU Series Installation, Operation & Maintenance Instructions Manual Download Page 10

Page 10

Use the procedure outlined below to initiate proper unit start-up:

When the disconnect switch is closed, high voltage is
present in some areas of the electrical panel. Exercise
caution when working with energized equipment.

1.

Turn all valves to their full open position. Turn on
the line power to all heat pump units.

NOTE: The units with scroll compressors are
tested for matched rotation of fan motor and
scroll compressors. At startup check fan
rotation, if fan rotation is correct all scroll
compressor will automatically have correct
rotation. If fan rotation is incorrect, interchange
any two power supply lead connections at
the disconnect. Scroll compressors with
INCORRECT rotation show following operating
characteristics:  1) High sound level  2)High
suction pressure  3) Low current draw.

2.

Operate each unit in the cooling cycle. Room
temperature should be  approximately 70

°

 to 75

°

 F

DB, and 61

°

 to 65

°

 F WB. Loop water temperature

entering the heat pumps should be between 70

°

 F

and 110

°

 F.

When the unit is operating in the cooling mode
under ARI conditions, the leaving water temperature
is approximately 10

°

 F warmer than the entering

water temperature at 3 GPM / ton.

a.

Turn  the unit thermostat to the cooling position.
If the unit has an optional MCO thermostat, set
the selector switch to COOL. Both the fan and
compressor should run.

For heat pumps with ACO, adjust the cooling
set point to a temperature at least 3

°

 F below

room temperature.

b.

Check for cool air delivery at the system grille
within a few minutes after the unit has begun to
operate. List the identification number of any
machines that do not function.

c.

Check the elevation and cleanliness of the
condensate lines. Dripping may be a sign of a
blocked line.

3.

Operate each heat pump in the heating cycle imme-
diately after checking cooling cycle operation. A
time delay will prevent the compressor from re-
starting for approximately 5 minutes.

NOTE: Large Commercial heat pump units are

UNIT START-UP

WARNING

designed to start heating at a minimum return air
temperature of 40

°

 F with normal water flow rate

and ambient temperature.

a.

If the unit has an optional MCO thermostat, set
the temperature indicator to the highest setting
and set the selector switch to HEAT. The fan
and the compressor should start.

If the unit has an optional ACO thermostat, set
the temperature indicator to the far right setting
and set the selector switch to AUTO. The fan
and the compressor should start.

b.

Once the unit has begun to run, check for warm
air delivery at the unit grille. List the serial
number of any machines that do not function.

4.

Establish a permanent operating record by logging
the unit operating conditions at initial start-up for
each unit.

5.

If a unit fails to operate, conduct the following
checks:

a.

Check the power supply. It should comply with
the electrical specifications described on the unit
nameplate.

b.

Look for wiring errors. Check for loose terminal
screws where wire connections have been made
on both the line and low-voltage terminal
boards.

c.

Check for dirty filters. A clogged filter will
cause safety cutouts to stop unit operation.

d.

Check the supply and return piping. They must
be properly connected to the inlet and outlet
connections on the unit.

e.

Check the fan. If the fan fails to operate, verify
that the fan wheel turns freely and that it is
secured to the shaft. Also verify that the fan
operates in both heating and cooling modes,and
rotates in the proper direction.

f.

If the checks described above fail to reveal the
problem and the unit still will not operate,
contact a trained service technician to ensure
proper diagnosis and repair of the equipment.

NOTE: Refer to Controller AOM provided
with the unit for status light operation and
fault codes

Summary of Contents for LCU Series

Page 1: ...Installation Operation Maintenance Instructions Large Commercial Series Water Source Heat Pumps LCU Series...

Page 2: ...Installation 3 Location and Access 4 Installation 4 Installation of Supply and Return Piping 4 Condensate Piping 5 Sound Attenuation for Large Commercial Units 6 Electrical Wiring 6 Wall Mounted Therm...

Page 3: ...after it is removed Inspection Upon receipt of shipment at the job site carefully check the shipment against the bill of lading Make sure all units have been received Inspect the carton or crating of...

Page 4: ...vicing of the compressor and coils without removal of the unit 3 Provide an unobstructed path to the unit within the closet or mechanical room to enable removal of the unit if necessary 4 Provide acce...

Page 5: ...to avoid condensate pan overflow at initial start up DO NOT bend or kink supply lines or hoses Optional pressure rated hose assemblies designed specifically for use with ClimateMaster units are availa...

Page 6: ...hock open the power supply disconnect switch and secure it in an open position during installation Use only copper conductors for field installed electrical wiring Unit terminals are not designed to a...

Page 7: ...nt of 40 F with entering air at 40 F entering water at 40 F and with both air and water at the stated flow rates of ARI Standard 320 96 rating test for initial winter start up Notes 1 These are not no...

Page 8: ...e to equal the rate of bleed 7 Refill the system and add trisodium phosphate in a proportion of approximately one pound per 150 gallons of water Reset the boiler to raise the loop temperature to about...

Page 9: ...ystem Water Temperature Ensure that it is within an acceptable range to facilitate start up When conducting this check also verify proper heating and cooling set points 3 System Water pH Verify system...

Page 10: ...e imme diately after checking cooling cycle operation A time delay will prevent the compressor from re starting for approximately 5 minutes NOTE Large Commercial heat pump units are UNIT START UP WARN...

Page 11: ...ore than 10 of the values noted on the unit nameplate Maintain a log of amperage values to detect deterioration prior to compo nent failure When replacing the compressor contactor or lockout relay in...

Page 12: ...d source the air coil Grounding the condensate overflow signal from the controller causes a fault after 30 continuous seconds Over Under Voltage When the controller senses a voltage over 30Vac or unde...

Reviews: