AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

MODULATING VALVE

CONFIGURATION

DEG

HEATING DELTA T                                            8

COOLING DELTA T                                          15

 PREVIOUS                                            NEXT 

3.5 VALVE 

CONFIGURATION

Confi gure temperature differentials at the thermostat for 
vFlow™ units with a motorized modulating valve.

Adjust the Valve Confi guration settings using the up/down 
arrow buttons.  Press the center button to select each item.

 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

NOTE 1:

 Minimum and Maximum degree values are shown 

only when the control is confi gured with the appropriate values.

NOTE 2: 

Refer to section 3.6.3 for multi-unit confi guration 

instructions.

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

PUMP CONTROL                                       FIXED

HEATING STAGE 1                                        60%

COOLING STAGE 2                                        75%

COOLING STAGE 1                                       50%

COOLING STAGE 2                                       70%

 PREVIOUS                                        SELECT 

 

3.5.1 

MODULATING VALVE OFF POSITION

 

Click Next from section 3.5 to select the off position 
value for the modulating valve.

 
 NOTE: 

For certain commercial multi-unit 

applications, the modulating valve can be kept 
slightly  open by choosing values 3.3-4.0.

MODULATING VALVE

CONFIGURATION

OFF POSITION                                               3.8

 PREVIOUS                                        SELECT 

3.6 MULTI-UNIT 

CONFIGURATION

If multiple units are connected to one ATC thermostat upon 
unit start-up, the thermostat will automatically register the 
serial numbers of all units connected to it.

NOTE: 

Multiple units may be connected directly to the ATC 

thermostat or connected to one another in series, as shown by 
the fi gure below.

Two 
connections 
on DXM2 
board to allow 
for multi-unit 
installation

Or

Summary of Contents for ATC32U01 iGate

Page 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Page 2: ...This page was intentionally left blank...

Page 3: ...ct airflow from supply registers In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being r...

Page 4: ...f 70 F your thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow...

Page 5: ...mation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO 78...

Page 6: ...multi stage compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up d...

Page 7: ...be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating mode using the up down arro...

Page 8: ...mum Heat LWT valid range based on specific model refer to model IOM Minimum Cool LWT valid range based on specific model refer to model IOM NOTE Refer to section 3 6 3 for multi unit configuration ins...

Page 9: ...3 for multi unit configuration instructions VARIABLE SPD INTERNAL PUMP CONFIGURATION PUMP CONTROL FIXED HEATING STAGE 1 60 COOLING STAGE 2 75 COOLING STAGE 1 50 COOLING STAGE 2 70 PREVIOUS SELECT 3 5...

Page 10: ...to remind the user to change the air filter after the selected time has passed Adjust the Air Filter Reminder settings using the up down arrow buttons Press the center button to save changes Cumulativ...

Page 11: ...nergized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation This logic w...

Page 12: ...COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0 PUMP SPEED 0 TEST MODE OFF SELECT OPTION PREVIOUS SELECT 9 2 CONTROL DIAGNOSTICS Control Diagnos...

Page 13: ...T OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating control DX...

Page 14: ...CC Y2 Y2 CO RV W W ACC1 O O OUTPT ACC2 G G FAN AL1 H H HWG EH1 OVR DH PUMP EH2 PREVIOUS FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 O...

Page 15: ...its are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The thermostat will reset a...

Page 16: ...contained herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system...

Reviews: