OPTION 07 — EQUIPMENT DDC CONTROLLER

 — 

This selection should be set to ON when control is to be 
used with ClimateMaster heat pump units, the DXM or 
CXM will take care of the timeguard and cycle timers. The 
minimum on time is still controlled by the thermostat. Off 
setting could delay compressor start by 12 minutes.

Selection: OF(F), ON
OF — Timeguard and cycle timers are enabled 
ON — Timeguard and cycle timers are disabled 
Default: OF (off)

OPTION 11 — DEADBAND BETWEEN HEATING 

AND COOLING SET POINTS 

— This selection allows 

the installer to choose how much differential will exist 
between the heating and cooling set points.

Selection: 1 to 10 (F or C)
Default: 5

OPTION 13 — SPACE TEMPERATURE DISPLAY 

ADJUSTMENT (OFFSET) 

— This configuration is 

the number of degrees to be added to the displayed 
temperature to calibrate or deliberately miscalibrate 
the measured space temperature. This selection is not 
available to the installer if Option 39 is set to SP (set 
point display).

Selection: –5 to 5 F (always in F) Default: 0

OPTION 15 — AUTO MODE AVAILABILITY 

— The 

ON selection will allow automatic changeover between 
heating and cooling as demand requires a mode 
selection. OF maintains either heating or cooling mode 
selection only.

Selection: ON, OF(F)
ON — Auto mode 
OF — Manual mode
Default: ON

OPTION 16 — MAX CYCLES PER HOUR

 — The 

maximum cycle rate is limited by internal timers to the 
selected number of cycles per hour. Selection of a higher 
number causes faster cycling resulting in more constant 
room temperature.

Selection: 4, 6, 8
4 — The Y1 output will be energized at most twice 
per hour. When an output is energized, it will not be 
energized again for 15 minutes.
6 — The Y1 output will be energized at most four 
times per hour. When an output is energized, it will 
not be energized again for 10 minutes.
8 — The Y1 output will be energized at most six times 
per hour. When an output is energized, it will not be 

energized again for 8 minutes.
Default: 4

OPTION 18 — BACKLIGHT CONFIGURATION

 —

When set to OF (off), the backlight will be lit for 10 
seconds after a button is pressed. After 10 seconds of no 
button presses, the backlight turns off.

When ON is enabled, the backlight will normally be 
on and dim in appearance. The backlight brightness 
becomes brighter when a button is pressed. After 10 
seconds of no button presses, the backlight will return to 
the dimmer level until another button press occurs.

Selection: OF(F), ON
Default: ON with 24 vac power; for batteries only, 
default is OFF.

OPTION 20 — OUTDOOR AIR TEMPERATURE 

DISPLAY ADJUSTMENT (OFFSET)

 — This selection 

is not available unless Option 02 is set to Od (outdoor 
air temperature) and a valid sensor is connected to S1 
and S2 terminals. It allows the calibration, or deliberate 
mis-calibration of the outdoor air temperature sensor 
reading.

Selection: –5 to 5 (number of degrees F added to the 
outdoor air temperature reading to “calibrate” the 
temperature sensor)
Default: 0

OPTION 21 — KEYPAD LOCKOUT WITH PASSCODE

 

— The thermostat is shipped with the keypad fully 
accessible. This option allows the installer to limit access 
to the keypad.

Selection: OF(F), 1, cd
OF — When set to OF, the user has full access to the 
keypad
1 — The user will only have access to modify the set 
points (within the set point limits of Option 26 and 
Option 27). The padlock icon will be displayed until 
the user presses and holds the up and down buttons 
simultaneously for five seconds to unlock the keypad. 
Once the keypad is unlocked, the user has full access 
to the thermostat functionality. The keypad returns 
to the locked condition after no buttons have been 
pressed for two minutes.
cd — The entire keypad is locked and the padlock 
icon is displayed. When the user presses a button 
the backlight turns on to maximum brightness for 10 
seconds and a “--” is displayed in the temperature 
setting. The user must enter the unlock code and 
press the mode button to unlock the thermostat. 
The padlock icon will then turn off and the user will 

Configuration

Summary of Contents for ATA11U03

Page 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Page 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Page 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Page 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Page 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Page 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Page 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Page 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Page 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Page 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Page 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Page 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Reviews: