background image

8

W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

will be displayed in the set-point location.
To initiate factory defaults, the installer then presses the 
mode button until the 10 is flashing. The installer then 
presses and holds the down button. While the down 
button is held, the 10 will count down from 10 to zero at 
a rate of 2 counts per second (5 seconds total). When the 
value reaches zero, all display segments are turned on for 
five seconds and the factory defaults are restored. If at 
any time during the countdown the installer releases the 
down button, the countdown terminates and the display 
returns to the starting value of 10.

Exiting Configuration Mode

 - To exit the configuration 

mode, press the fan button.

SYSTEM START-UP AND CHECKOUT
Installer Test Mode

 — This thermostat has a built-

in installer test capability. It allows easy operation of 
equipment without delays or set point adjustments to 
force heating or cooling. To enter installer test mode, 
press and hold the fan button for 15 seconds (after 10 
seconds installer configuration is entered; a continuous 
15 seconds and installer test is entered). At the start of 
installer test, the mode is Off, the fan is “fan auto” and 
the set point display displays “InS.”

NOTE: Unit must be powered up and CXM/DXM 

in test mode to disable unit timers or compressor 

not energized for more than 5 minutes.

The mode button is used to change the system operating 
mode to test the heating and cooling equipment. Auto 
mode is not available during installer test.

When the mode is set to heat, “H” is displayed, heating 
is energized for 180 seconds. During the installer test 
operation, the “on” icon is displayed.

At the end of the equipment test cycle the mode returns to 
OFF.

The LCD display counts down the time remaining 
(in seconds, from 180 to 0) for each stage when the 
equipment is energized. See Fig. 5.

The same procedure is repeated for the cool mode. “C” 
is displayed when cooling is active.

The test of a heating or cooling cycle can be terminated 
before the timer counts down to zero by pressing the 
mode button.

Pressing the fan button alternates the fan selection 
between fan auto and fan on and the fan output follows 
accordingly. There is no timer associated with the installer 
testing of the fan operation.

Terminating Installer Test

 — After 15 minutes of no 

button presses by the installer, installer test is terminated.

Pressing the up button, down button, or cycling 
thermostat power at any time during installer test 
terminates the installer test and returns the thermostat to 
normal operation.

Figure 5: Installer Test Mode

Checklist

 — The following installer checklist should be 

performed after completing installation:
1.  Run equipment through several heating and cooling 

cycles to ensure proper operation. To operate the 
thermostat in its normal operating mode, consult the 
User Operating Manual.

2.  If the equipment is to be left in operation, the 

set points and operating mode must be properly 
selected.

3.  Put away tools and instruments and clean up debris.
4.  Review and leave this manual and User Operating 

Manual with owner.

 

 

Summary of Contents for ATA11U03

Page 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Page 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Page 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Page 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Page 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Page 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Page 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Page 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Page 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Page 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Page 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Page 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Reviews: