G e o t h e r m a l   H e a t   P u m p   S y s t e m s

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

LOOP OPTION                                        SINGLE 

PUMP CONTROL                                       FIXED

HEATING STAGE 1                                        60%

COOLING STAGE 2                                        75%

COOLING STAGE 1                                       50%

COOLING STAGE 2                                       70%

 PREVIOUS                                        SELECT 

3.4 PUMP 

CONFIGURATION

vFlow™ vs internal fl ow control pump can be controlled either 
through temperature differential (Delta T) or can be set to 
specifi c speed (fi xed; % of full speed for each heat and cool 
stage).

Can be confi gured for either single pumping or parallel 
pumping.

Confi gure temperature differentials at the thermostat for 
vFlow™ units with an internal fl ow control pump.

Adjust the Pump Confi guration settings using the up/down 
arrow buttons.  Press the center button to select each item.
 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

Maximum Heat LWT (valid range based on specifi c model; 
refer to model IOM). Minimum Cool LWT (valid range based 
on specifi c model; refer to model IOM).

NOTE: 

Refer to section 3.6.3 for multi-unit confi guration 

instructions.

To control vs pump by fi xed speed, select ‘Pump Control’, 
press  , use down arrow to select ‘Fixed’, and press   to 
save.

Default stored in control. Valid range: 15% - 90% (in 1% 
increments)
Heating Stage 1   

Cooling Stage 1

Heating Stage 2   

Cooling Stage 2

If Pump Confi guration is set to ‘VS PUMP PARALLEL’, valid 
range changes to 50-90% (in 1% increments).

3.5 VALVE 

CONFIGURATION

Confi gure temperature differentials at the thermostat for 
vFlow™ units with a motorized modulating valve.

Adjust the Valve Confi guration settings using the up/down 
arrow buttons.  Press the center button to select each item.
 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

NOTE 1: Minimum and Maximum degree values are shown 
only when the control is confi gured with the appropriate 
values.

NOTE 2: Refer to section 3.6.3 for multi-unit confi guration 
instructions.

3.5.1  MODULATING VALVE OFF POSITION

For certain commercial multi-unit applications, the modulating 
valve can be kept slightly open by choosing values 3.3-4.0.

MODULATING VALVE

CONFIGURATION

OFF POSITION                                               0.0

VALVE CONTROL DELTA T

HEATING DELTA T                                           7 F

COOLING DELTA T                                        10 F

MAXIMUM HEAT LWT                                    80 F

MINIMUM COOL LWT                                    40 F

 PREVIOUS                                        SELECT 

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

LOOP OPTION                                   PARALLEL

PUMP CONTROL                                   DELTA T

HEATING DELTA T                                           7 F

COOLING DELTA T                                        10 F

MAXIMUM HEAT LWT                                    80 F

MINIMUM COOL LWT                                    40 F

 PREVIOUS                                        SELECT 

Summary of Contents for ACDU03

Page 1: ...orking properly and or may void the warranty on both the thermostat and the equipment Section Title Page 1 0 Connection 3 2 0 Menu Structure 4 3 0 System Configuration 4 3 1 Airflow Selection 4 3 2 Option Selection 5 3 3 Unit Configuration 5 3 4 Pump Configuration 6 3 5 Valve Configuration 6 3 6 Multi Unit Configuration 7 4 0 Service Mode 8 4 1 Manual Operation 8 4 2 Control Diagnostics 8 4 3 Dips...

Page 2: ...This page was intentionally left blank ...

Page 3: ...nit by operating it manually performing control diagnostics viewing dip switch configurations or by viewing fault history and operating conditions when a fault occurred The Service Tool connects to the DXM2 board with a 4 Wire Connector as shown below P1 Alarm O Y1 Y2 W G C R AL1 R C R NSB AL2 JW1 P2 P5 B Gnd A 24V Service tool connection DXM2 Board DXM2 DXM2 Board Board 1 0 Connection WARNING WAR...

Page 4: ...tem has no blower Note 2 The Pump Configuration menu section 3 4 will not be present if the connected communicating control is configured for No Loop Configuration OTHER Note 3 The Valve Configuration menu section 3 5 will not be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating m...

Page 5: ...efore restarting NOTE 2 If multiple units are connected to one thermostat refer to section 3 6 for unit selection 3 3 UNIT CONFIGURATION Adjust the Unit Configuration settings including Heat Pump Family Heat Pump Size Blower Type and Loop Configuration using the up down arrow buttons Press the center button to select each item Heat Pump Family default stored in control valid range TE TY TES TEP TR...

Page 6: ...ol press use down arrow to select Fixed and press to save Default stored in control Valid range 15 90 in 1 increments Heating Stage 1 Cooling Stage 1 Heating Stage 2 Cooling Stage 2 If Pump Configuration is set to VS PUMP PARALLEL valid range changes to 50 90 in 1 increments 3 5 VALVE CONFIGURATION Configure temperature differentials at the thermostat for vFlow units with a motorized modulating va...

Page 7: ... to the ATC thermostat or connected to one another in series as shown by the figure below 3 6 1 MULTI UNIT AIRFLOW SELECTION In section 3 1 when an installer selects Airflow Selection from the System Configuration menu the installer may choose the unit to configure by the last 4 digits of its serial number from the following screen 3 6 2 MULTI UNIT OPTION SELECTION In section 3 2 when an installer...

Page 8: ... pump at the thermostat Navigate between diagnostic screens using the left right arrow buttons NOTE The Pump Status will not be present if the connected communicating control DXM2 is not configured for Pump section 3 4 SERVICE MODE MANUAL OPERATION CONTROL DIAGNOSTICS DIPSWITCH CONFIG FAULT HISTORY CLEAR FAULT HISTORY SELECT OPTION PREVIOUS SELECT MANUAL OPERATING MODE Y1 COMM OUTPUT OFF Y2 COMM O...

Page 9: ...TSTAT 4 ON RV O THERMOSTAT 5 ON DEHUMID OFF 6 ON EH2 AUX HEAT 7 ON BOILERLESS 8 ON SEE DXM2 AOM PREVIOUS NEXT CONTROL CONFIGURATION DIPSWITCH S2 1 ON ACCESSORY 1 2 ON ACCESSORY 2 3 ON 4 ON ACCESSORY 2 5 ON ACTIVE W COMP 6 ON 7 ON H DEHUM INPUT 8 ON FACTORY SETTING PREVIOUS NEXT CONTROL CONFIGURATION DIPSWITCH S3 1 ON FACTORY SETTING 2 OFF HWG TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SE...

Page 10: ...TIONS FAULT I O CONDITIONS FAULT CONFIG COND FAULT POSSIBLE CAUSES PREVIOUS SELECT FAULT TEMPERATURE CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 LT1 TEMP 28 1 LT2 TEMP 97 3 HOT WATER EWT 121 5 COMP DISCHARGE 157 7 LEAVING AIR 92 7 LEAVING WATER 34 9 ENTERING WATER 42 1 CONTROL VOLTAGE 26 4 PREVIOUS FAULT I O CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 TSTAT SAFETY OUTPT CONV COMM H...

Page 11: ...ult History will clear all fault codes stored in the thermostat as well as the fault history in any connected communicating controls DXM2 AXM FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 ON 3 OFF 4 ON 4 ON 4 OFF 5 ON 5 ON 6 ON 6 ON LT1 WELL 7 ON 7 ON LT2 WELL 8 ON 8 ON PREVIOUS POSSIBLE FAULT CAUSES LOW WATER COIL TEMP LOW WATER TEM...

Page 12: ...ined herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products ClimateMaster Inc 2012 97B0106N01 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com Rev Janua ry 2 3 2 0 1 9 Date Page Description 23 Jan 19 3 4 Update harness and service tool par...

Reviews: