REV. 2015-SEP-13
Clima-Flex S.A. de C.V.
15
5.1.2. CONTROL PANEL INSPECTION
●
Check the control panel to ensure that it is free of foreign objects.
●
Energize the unit with 3 phase electrical power. Phase unbalance must less than
2% of average.
●
Cycle each fan to assure rotation is correct
●
Cycle water pump (if applicable) to ensure that it is correctly energized.
¡CAUTION!
CLIC
* units are equipped with scroll compressors which must rotate freely or mayor damage to the
compressor may happen. Check rotation previously.
5.2. STARTUP
After finishing the inspection of the previous installation points and making sure all
the unit’s items
are correct the unit may be started.
1. UNIT CONTROL
Set the UNIT CONTROL switch on the ON position (Fig 2) to energize the control panel with 24
Volts.
After energizing the controller, wait five minutes for the unit to be on line and ready.
2. ON/OFF
Operation sequence will initiate by checking all security pre-programed points on the unit. If all
required conditions are OK the unit will be ready to initiate operation.
To start operation set the ON/OFF switch (Fig 2) to the ON position.
After six seconds the controller will command the start of the water pump.
If water flow is detected on the pipes, the internal sequence of the unit will begin.
Summary of Contents for CLIC SERIES
Page 1: ...REV 2015 SEP 13 Clima Flex S A de C V 1 CLIC SERIES INSTALLATION MANUAL ...
Page 6: ...REV 2015 SEP 13 Clima Flex S A de C V 6 1 2 INSTALLATION DIAGRAM ...
Page 7: ...REV 2015 SEP 13 Clima Flex S A de C V 7 2 NOMENCLATURE ...
Page 8: ...REV 2015 SEP 13 Clima Flex S A de C V 8 3 ELECTRICAL DIAGRAMS ...
Page 9: ...REV 2015 SEP 13 Clima Flex S A de C V 9 ...
Page 10: ...REV 2015 SEP 13 Clima Flex S A de C V 10 4 DIMENSIONES ...
Page 11: ...REV 2015 SEP 13 Clima Flex S A de C V 11 ...
Page 17: ...REV 2015 SEP 13 Clima Flex S A de C V 17 CLIC SERIES MAINTENANCE MANUAL ...
Page 19: ...REV 2015 SEP 13 Clima Flex S A de C V 19 CLIC SERIES CONNECTION MANUAL ...
Page 24: ...REV 2015 SEP 13 Clima Flex S A de C V 24 1 3 HYDRAULIC CONNECTION DIAGRAM ...