Installation:
This EBS4N-LI Surface mount non-maintained Emergency Luminaire can be installed on solid surface
or used to replace an existing unit.
•
Locate the installation position.
•
Refer Images and Dimensions below for the Cut-out Hole and other dimensions.
•
Pre-drill mounting holes
•
Mount base plate and use suitable fixings to secure the base plate into the pilot holes
•
Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount
conduit entry)
•
Terminate the supply cables to the L, N & E terminals
•
Install the top cover, containing the control gear, ensuring to reconnect the control gear assembly
to the connector from the supply terminal block
•
Ensure the Battery is connected
•
Screw the cover to the base plate and, in the case of side/conduit entry remove the knock-out at
the end of the cover to go cover the conduit
Dimensions:
Testing:
When the EBS4N-LI unit is connected to the un-switched active, it must be allowed to charge the battery
for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the following
tests:
•
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
•
Press and hold Test Button for each LED head or switch Off Mains Supply, check that the
emergency lamps are On.
•
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.