background image

1942340 V1.2 

17 May 2021 

 

Installation: 

This LWPLIFEz-PRO Surface mount Emergency Luminaire can be installed on solid or T-BAR ceilings 

or used to replace an existing unit. 

 

Locate the installation position. 

 

Pre-drill mounting holes per diagram below. 

 

Removed fitting cover. 

 

Use suitable fixings to fasten the fitting to the mounting surface. 

 

Taking note of the terminal block position, drill a hole in the fitting box to suit the cable gland or 

conduit to be used for power entry. 

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Screw the cover to the base. 

 

If the CTP capabilities are activated, please affix the CTP status Label to a visible surface.  

 

This luminaire contains non-user replaceable light source and battery. 

 

The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer 

than 0.330m is not expected. 

 

Images and Dimensions: 

 

 

Note: 

This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-

user replaceable light source and battery - to be replaced (if required, refer installation instructions for 

battery replacement) by Clevertronics service personnel/agents or a registered electrician.

 

 

 

 

 

 

 

 

 

Battery Replacement: 

1.  Prior to any work, isolate the power to the luminaire that requires battery replacement. 

2.  Open the fitting by loosening the four corner screws holding diffuser, support diffuser during this. 

3.  Remove four screws holding opaque lamp holder plate, support lamp holder plate during this. 

4.  Remove four stand-offs holding the gear tray, support gear tray during this process. 

5.  Remove the Battery Connector from the Emergency Driver.  

6.  Remove the battery from the gear tray by removing mounting screws.  

7.  Replace battery, re-install screws and connect to Emergency Driver. 

8.  Reinstall the gear tray, lamp holder plate and diffuser, ensure diffuser is aligned on seals to 

maintain the weatherproof seal. 

 

Testing Procedure:

 

When the unit is connected to the un-switched active, it must be allowed to charge the battery for at 

least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests: 

 

 

The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the 

unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation 

and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:   The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The Li-ion battery in the Exit & Emergency Unit has been selected to give 

excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery 

cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty 

claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

https://clevertronics.co.uk/product-warranty-statement/

 

 

 

 

Reviews: