10
2. Electrical Connection Data
Minimum wire gauge required for field connection
Attention: always observe local ordinances!
OEB & OES 6.10
Volts 208 240
Phase 3
3
Hz 60 60
Amps 27.3 30.8
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
12 10
OEB & OES 6.20 AND 10.10
Volts 208 240
Phase 3
3
Hz 60 60
Amps 45.5 51.8
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
6 6
OEB & OES 10.20 AND 12.20
Volts 208 240
Phase 3
3
Hz 60 60
Amps 77.3 88.3
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
3 2
OEB & OES 20.10
Volts 208 240
Phase 3
3
Hz 60 60
Amps 91 103.6
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
2 2
OEB & OES 20.20
Volts 208 240
Phase 3
3
Hz 60 60
Amps 149.9 171.9
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
2/0 3/0
OEB & OES 20.20
Volts 440 480
Phase 3
3
Hz 60 60
Amps 84 91
Wires
3 + Ground
3 + Ground
Wire Size, Cu, 90°C
AWG
3 2