background image

CB780E/CB784E RELAY MODULES WITH VALVE PROVING

750-234

27

32-00150—03

OPERATION

Sequence of Operation

The CB780E/CB784E has the following operating 
sequences, see Fig. 8–10. The CB780E/CB784E LED 
provide positive visual indication of the program 
sequence: POWER, PILOT, FLAME, MAIN and ALARM.

Initiate

The CB780E/CB784E enters the INITIATE sequence when 
the Relay Module is powered. The CB780E/CB784E can 
also enter the INITIATE sequence if the Relay Module 
verifies voltage fluctuations of +10/-15 percent or 
frequency fluctuations of +/-10 percent during any part of 
the operating sequence. The INITIATE sequence lasts for 
ten seconds unless the voltage or frequency tolerances 
are not met. When the tolerances are not met, a hold 
condition is initiated and displayed on the VFD for at least 
five seconds. When the tolerances are met, the INITIATE 
sequence restarts. If the condition is not corrected and the 
hold condition exists for four minutes, the 
CB780E/CB784E locks out. Causes for hold conditions in 
the INITIATE sequence:

a. AC line dropout is detected.
b. AC line noise prevents a sufficient reading of the 

line voltage inputs.

c. Low line voltage brownouts occur.

The INITIATE sequence also delays the burner motor 
starter from being energized and de-energized from an 
intermittent AC line input or control input.

Standby

The CB780E/CB784E is ready to start an operating 
sequence when the operating control determines a call for 
heat is present. (Terminal 6, or Terminal 17 if Valve Proving 
is required.) The burner switch, limits, operating control 
and all microcomputer monitored circuits must be in the 
correct state for the CB780E/CB784E to continue into the 
PREPURGE sequence.

Pre-Purge

Purge timers provide Pre-Purge timings selectable from 
30 seconds to 2 1/2 minutes:

a. The operating control (terminal 6, or terminal 17 

for valve proving), Running Interlocks, Pre-Igni-
tion Interlocks, Burner Switch, Run/Test Switch, 
Lockout Interlocks and all microcomputer moni-
tored circuits must be in the correct operating 
state.

b. The blower motor output, terminal 5, is powered 

to start the PREPURGE sequence. The firing rate 
motor is driven to the high fire position. The PRE-
PURGE timing does not begin until the Lockout 
Interlock String and High Fire Switch are both 
closed.

c. If Before, Split or Both Valve Proving tests are 

selected (and demand input T17 is used), the 
CB780E/CB784E will sequence the main valves 
to conduct the VP tests concurrently with Pre-
Purge (beginning at 10 seconds into the purge 
time).

d. The Pre-Ignition Interlock input must remain 

closed throughout PREPURGE (except during VP 
testing); otherwise, safety shutdown occurs for 
the CB780E/CB784E.

e. The Lockout Interlock inputs (interlock circuit 

including Airflow Switch) must close by ten sec-
onds after demand; otherwise, a safety shutdown 
for the CB780E/CB784E occurs.

f.

When PREPURGE timing is complete, the firing 
rate motor drives to the low fire position.

g. When the firing rate motor reaches low fire posi-

tion, the Low Fire Switch, terminal 18, input must 
be energized before entering the Ignition Trial 
state.

Ignition Trials—Pilot Lighted System 
(Except VP System with DSI)

1.

Pilot Flame Establishing Period (PFEP):
To get pilot lighted system on VP system, Jumper 2 
must be removed. Default is direct spark ignition.
a. With the firing rate motor at the low fire position:

(1) With the demand on terminal 6, the pilot valve 

and ignition transformer, terminals 8, 10 and 
21, are energized. With the demand on termi-
nal 17 (operating as Valve Proving), the 
CB780E/CB784E has a 15-second inter-
rupted pilot valve, terminal 21. The 
CB780E/CB784E have a ten-second inter-
rupted pilot valve/ignition, terminal 8. Termi-
nal 21 is Main Valve 2 only.

(2) During PFEP, the Low Fire Switch must 

remain closed. If it opens, a safety shutdown 
occurs.

(3) The Pre-Ignition Interlock input is ignored 

throughout the Ignition Trial state.

b. Flame must be proven by the end of the ten-sec-

ond PFEP (four if JR1 is clipped) to allow the 
sequence to continue. If flame is not proven by 
the end of PFEP, a safety shutdown occurs.

c. After five seconds, the ignition, terminal 10, is 

de-energized for early spark termination.

2.

Main Flame Establishing Period (MFEP):
a. Terminal 9 (and 21 in VP mode) is energized 

when the presence of flame is verified at the end 
of a 10-second Pilot Flame Establishing Period 
(PFEP) (four seconds if JR1 is clipped).

b. Terminal 8 is turned off 10 seconds after Termi-

nal 9 (and Terminal 21) is energized.

c. Terminal 21 action demand on Terminal 6 (with-

out Valve Proving Function) is de-energized 15 
seconds after Terminal 9 is energized.

Ignition Trials—Valve Proving with DSI 
System

1.

Demand connected to Terminal 17:

JR2 Intact on the CB780E/CB784E

a. Ignition, Main Valve 1 and Main Valve 2, Termi-

nals 10, 9, and 21 turn on together.

b. Flame must be proven at the end of the 4 second 

Main Flame Establishing Time.

c. Ignition, Terminal 10 is turned off. System now in 

Run.

d. If Flame is not proven, safety lockout occurs.

Summary of Contents for 833-03517

Page 1: ...leshooting The CB780E CB784E offer the Valve Proving test feature Using the 833 2727 Keyboard Display standard on the CB780E the following features can be set up Post Purge time Up to 60 minutes Devic...

Page 2: ...etaining history files and sequencing status after loss of power Remote reset optional Report generation optional Five sequence information LEDs Burner controller data Sequence status Sequence time Ho...

Page 3: ...Line Voltage Supply L1 b 5 Burner Motor 9 8AFL 58 ALR inrush 6 Burner Controller and Limits Demand Not Valve Proving 1 mA 7 Lockout Running Interlock 8A run 43A inrush 8A run 43A inrush 8 Pilot Valve...

Page 4: ...or 12 times a minute during burner operation and shuts down the burner if the detection system fails Series 4 amplifiers check 60 to 120 times per minute SIL 3 Capable SIL 3 Capable in a properly desi...

Page 5: ...and CB784E are identical except for the Keyboard Display Module which is standard with the CB780E and optional with the CB784E A 4 line LCD display option S78000A1092 U is available to be purchased se...

Page 6: ...present after 240 seconds b Pre Ignition Interlock is open an accumulative time of 30 seconds c Interlock check feature is enabled only with JR3 clipped and the Interlock String including the airflow...

Page 7: ...o line voltage inputs to verify proper operation in the presence of normal electrical line noise such as transient high voltage spikes or short periods of line dropout Signal conditioning is tolerant...

Page 8: ...ark Termination The ignition terminal is monitored to verify early spark termination five seconds ignition and pilot and five seconds pilot only First Out Annunciation and Self Diagnostics Sequence St...

Page 9: ...ts and interlocks must be rated to simultane ously carry and break current to the ignition trans former pilot valve and main fuel valve s 6 All external timers must be listed or component rec ognized...

Page 10: ...o blow out resulting in dead unpowered system WARNING b Keyboard Display Module For communications purposes use an unshielded 22 AWG 2 wire twisted cable and one wire for ground if the lead wire run a...

Page 11: ...hat modules on the closest and farthest end of the daisy chain con figuration string require a 120 ohm 1 4 watt M28586A CONFIGURATION JUMPERS MICROCOMPUTER RESET PUSHBUTTON RUN TEST SWITCH STATUS LEDs...

Page 12: ...etector leadwires 1 Do not run high voltage ignition transformer wires in the same conduit with the flame detection wiring 2 Do not route scanner wires in conduit with line voltage circuits 3 Enclose...

Page 13: ...ON TRANSFORMER 2ND STAGE FUEL VALVE OPTIONAL R W B R W B L1 HOT L2 1 8 9 10 L2 833 2725 15 SEC INTERRUPTED PILOT VALVE 2 1 3 3 HIGH FIRE PURGE SWITCH 2 POWER 00 OPERATING CONTROLS AND INTERLOCKS BURNE...

Page 14: ...ALVE CLOSEST TO THE BURNER JR2 REMOVED FOR PILOT SEQUENCE 1 TIMED PREPURGE POWER FLAME MAIN PILOT ALARM POWER FLAME MAIN PILOT ALARM ALARM ALARM ALARM 00 IC SSC LED DISPLAY PII MV2 21 1 2 2 M28583A G...

Page 15: ...ER POST PURGE FINISH POST PURGE HF T19 CLOSED 1 1 832 1693 120 OHM RESISTOR 832 1693 120 OHM RESISTOR 1 A B A B C C GND 13 VDC RESET 1 2 3 4 5 1 2 3 MOMENTARY PUSH BUTTON SWITCH 833 2727 KEYBOARD DISP...

Page 16: ...ews securely without deforming the plastic Installing the Purge Card 1 Remove the Keyboard Display Module or DATA CONTROLBUS MODULE see Fig 16 or 17 2 Remove the current Purge Card from the CB780E CB7...

Page 17: ...d installation Fig 16 Keyboard Display Module installation Fig 17 Data ControlBus mounting Remote Mounting of Keyboard Display Module 1 The Keyboard Display Module can be mounted either on the face of...

Page 18: ...80E CB784E retaining clasp 4 Verify the amplifier is firmly in place 5 Perform all required checkout tests Installing the Flame Detector NOTE Table 5 lists the flame detection systems avail able for u...

Page 19: ...ernal Safety Relay dropout state and concurrent with Post Purge if configured Both Valve proving occurs at both times Before and After noted above Split The downstream seat high pressure test is per f...

Page 20: ...Switch Selection 1 Determine the maximum operating inlet pressure for the upstream valve for example 5 0 psi 140 in wc 2 Divide the inlet pressure by two 2 5 psi 70 in wc for example 3 From column 2 i...

Page 21: ...usly Fig 23 Select Restart screen 7 To get to the next screen press the down arrow Get ting Data will be displayed then the following screen Fig 24 SETUP Valve Prove screen NOTE This screen sets up wh...

Page 22: ...l remain energized after the demand ends NOTE The device comes standard with 15 second Post purge 13 Use the buttons to adjust the postpurge time Time changes 0 to 60 seconds in 1 second intervals 60...

Page 23: ...Done screen 23 Press and hold the relay module RESET button for five seconds to program the Valve Proving setup into the relay module The Release Reset screen will appear on the KDM Fig 38 Release Re...

Page 24: ...on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used...

Page 25: ...eck the Items Listed Below 1 All None 4 L2 Line voltage at Terminal 4 1 Master Switch 2 Power connected to the Master Switch 3 Overload protection fuse circuit breaker etc has not opened the power lin...

Page 26: ...13 19 L2 Firing rate motor drives open line voltage at Terminal 19 after motor is in High Fire position 1 High Fire Purge Switch 2 Firing rate motor and transformer 14 All 4 5 and 14 13 19 L2 Firing...

Page 27: ...sequence the main valves to conduct the VP tests concurrently with Pre Purge beginning at 10 seconds into the purge time d The Pre Ignition Interlock input must remain closed throughout PREPURGE exce...

Page 28: ...NDBY PURGE PILOT IGN MAIN IGN RUN and POST PURGE timing information PURGE PILOT IGN MAIN IGN and POSTPURGE in minutes and seconds hold information PURGE HOLD T19 and lockout information Lockout Fault...

Page 29: ...ER PILOT FLAME MAIN AND ALARM PURGE DELAY High Fire Jumprd POWER PILOT FLAME MAIN AND ALARM PURGE HOLD TEST Run Test Switch POWER PILOT FLAME MAIN AND ALARM PURGE DELAY Low Fire Jumprd POWER PILOT FLA...

Page 30: ...of selectable messages to a subset of selectable mes sages The tu push button can also be used to change from a subset message to a first level select able message The symbol located on the second in...

Page 31: ...up o arrows until the desired second line is displayed Press the ENTER func tion Fig 44 SAVE Function c The following Display will appear Fig 45 Save Display Exit screen d Press the push button to sav...

Page 32: ...ne msg H1 Fault Cycle nnnnn H2 Fault Hours nnnnn H2 Fault Code nnn H2 fault message H2 sequence message H2 second line msg H2 Fault Cycle nnnnn H3 Fault Hours nnnnn H3 Fault Code nnn H3 fault message...

Page 33: ...0 DI Preignition Interlock PreIgn ILK 1 or 0 DI Pilot Valve First State Oil Valve Valv Start V25 1 or 0 DI Jumper 1 INTACT or CLIPPED DI Jumper 2 INTACT or CLIPPED DI Jumper 3 INTACT or CLIPPED DI Am...

Page 34: ...d Line First Line Message Expanded Annun Expanded Annunciator EA not connected Current status CS a EA Message Valve Closure Valve Close T4 1 or 0 EA Burner Switch Burner Sw T5 1 or 0 EA Operating Cont...

Page 35: ...zzle In any case do not exceed the nominal lightoff time specified by the equipment manufacturer close the manual fuel shutoff valve s if the flame is not burning at the end of the specified time WARN...

Page 36: ...stable voltage disregarding the peaks and valleys caused by the self checking oper ation 6 The meter reading must be as specified in Table 8 after all tests are completed and all adjustments are made...

Page 37: ...ignition terminals 8 10 or 21 refer to the appropriate wiring diagram to determine the proper terminal Disconnect the leadwire to the pilot valve if it is connected to the same terminal c Close the m...

Page 38: ...should start the ten second INITIATE sequence 5 Let the sequence advance through PREPURGE Ignition spark should occur after PREPURGE period Listen for the click of the first stage fuel solenoid valve...

Page 39: ...ure reading at the exact point the FLAME LED light goes out 9 Increase the pilot pressure immediately until the FLAME LED comes on and then turn it down slowly to obtain a pressure reading just above...

Page 40: ...ions and the equipment Operating Manual Continue adjustments until hot refractory hold in is eliminated Ultraviolet Sensor Ignition Spark Response Test All Ultraviolet Detectors Test to make certain t...

Page 41: ...occur 5 Failure to ignite main a Open the manual pilot valve s leave the main fuel manual shutoff valve s closed b Depress the reset button c Start the system d The pilot should ignite and the flame...

Page 42: ...switch label seal It is intended to prevent and detect unauthorized access Modbus DDL Interface security Any conducts critical to device functionality DDL Modbus lines etc shall be physically protect...

Page 43: ...tacts are free from contaminants 4 Reset and sequence the relay module to Pre Purge place the TEST RUN Switch in the TEST position if available Measure the voltage between ter minal 7 and G ground lin...

Page 44: ...Ignition Interlock status 5 If the fault persists replace the relay module Code 5 2 High Fire Sw or Low Fire Sw Either High Fire Switch or Low Fire Switch failure 1 Check wiring and correct any error...

Page 45: ...nals and can display the status of the terminal at the KDM example Pilot Valve T8 ON See Table 11 for a complete terminal description and number The display will show the actual status of the terminal...

Page 46: ...yout 3 Use appropriate Results column items to fill in the Valve Train Volume Formula and the Calculation of Valve Proving Test Time 4 Round up the time to the nearest second 5 The test time calculate...

Page 47: ...ze NPT in 2 in NPT 19 3 356 A L Pipe Length ft 1 75 ft 1 75 L P Valve Inlet Pressure psig a 2 2 P C Burner Maximum Firing cf hr b 2 5 mbtu 2500 C Table 17 V1 Upstream Volumes for Valves Models Pipe Si...

Page 48: ...DULES WITH VALVE PROVING U S Registered Trademark 2018 Honeywell International Inc 32 00150 03 M S Rev 01 18 Printed in U S A 750 234 Fig 50 Flush mounting of a Keyboard Display Module template M5082C...

Reviews: