CB780E/CB784E RELAY MODULES WITH VALVE PROVING
750-234
23
32-00150—03
17.
Use the down arrow to confirm correct.
NOTE:
Using the up arrow during this step will take you
back to the beginning of the setup routine.
“Getting Data” will be displayed.
Fig. 33. Confirm screen.
18.
Press Enter.
Fig. 34. Confirm Correct screen.
19.
Use the down arrow to confirm correct.
“Getting Data” will be displayed.
The following steps are used to confirm your selection.
Fig. 35. Confirm Postpurge time.
20.
Press Enter.
Fig. 36. Confirm correct/incorrect screen.
21.
Press Enter.
22.
Press the down arrow to confirm the correct post-
purge time. “Getting Data” will be displayed until the
screen in Fig. 32 appears.
Fig. 37. Setup Done screen.
23.
Press and hold the relay module RESET button for
five seconds to program the Valve Proving setup into
the relay module.
The Release Reset screen will appear on the KDM.
Fig. 38. Release Reset screen.
Once the system is in operation, the settings of the Valve
Proving and Postpurge can be viewed in Diagnostics,
using your 833-2727 Keyboard Display Module (KDM).
Future changes to the Valve Proving and Postpurge
features are still possible. With the relay module in
standby, scroll to the Setup line and enter the password to
change the settings.
CONFIRM: ValveProve
VP Time: 00:30 ?
M22672B
SC
BACK
ENTER
Edit:
-
+
=Confirm correct
=Incorrect
M22671C
BACK
ENTER
Edit:
-
+
M22674B
BACK
ENTER
Edit:
-
+
CONFIRM: Postpurge
±PostTime: 00:30 ?
SC
=Confirm correct
=Incorrect
M22671C
BACK
ENTER
Edit:
-
+
SETUP DONE: Press
Reset for 5 sec . . .
M22676C
BACK
ENTER
Edit:
-
+
SETUP DONE:
... release Reset
M22765C
BACK
ENTER
Edit:
-
+