![Clearfield FieldSmart FxMP Installation Manual Download Page 7](http://html1.mh-extra.com/html/clearfield/fieldsmart-fxmp/fieldsmart-fxmp_installation-manual_2621163007.webp)
7
FieldSmart
®
FxMP Panel & Standard Frame
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • [email protected]
Manual 019807 REV A - June 2018
Standard Frame Raised Floor Installation
Note:
Raised floor mounting hardware is NOT included with the standard frame. Hardware is sold as a separate line item
(Clearfield P/N 011236).
IMPORTANT: If your frame is to be mounted next to a wall, or there are multiple frames in a line up, you MUST
install the interbay management and end guards BEFORE mounting the frame to the floor.
Tools:
• Hammer (or rotary) drill (depth gauge recommended)
• 5/8” masonry drill bit
• Socket wrench set
• Blowout air bulb or vacuum with small diameter tube
Also required is a raised floor mounting kit (Clearfield P/N 011236).
1. 1/2-13 Hex Nut (Qty 8)
2.
1/2 Lock Washer (Qty 4)
3.
1/2 Flat Washer (Qty 4)
4. 1/2-13 x 30 Threaded Rod (Qty 4)
5. Hilti HDI 1/2” Anchor (Qty 4)
6. 1/4 x 2” Flatwasher .515 Hole (Qty 8)
7. Split Tubing 30” (Qty 4)
Screw Sequence for Floor
Screw Sequence for Frame
Note:
Clearfield recommends installing the anchors directly into the concrete floor.