At the rectifier shelf, open the fuse panel door. Verify that the battery breaker is OFF.
Remove the battery compartment door. See Operating Cabinet Doors for instructions.
Remove the front retainer bracket from the battery tray.
Note:
If you are using the optional battery heater, install the heater before installing batteries. See Installing a
Battery Heater for instructions.
In the battery compartment, disconnect the #8 AWG battery power cables from the power supply leads and set
the cables aside.
Place a string of four batteries partially into the battery compartment, arranged with the terminals accessible
in front.
Note:
You will slide the batteries into the battery tray after installing the cables and protective covers.
Connect the battery power cables as follows:
a.
Remove the protective caps from the cable ring lugs.
b.
Attach the black cable to the positive (+) terminal post at the positive
end of the string.
c.
Attach the red cable to the negative (-) terminal post at the negative end
of the string.
ALERT!
Check all connections carefully to verify correct wiring polarities.
d.
Install the temperature sensor cable lug onto the string’s negative (-) terminal post.
e.
Tighten the hardware on the terminal posts to the torque specified by the manufacturer.
Install the three jumper cables between the battery terminal posts using the supplied flat washers, split lock
washers, and bolts.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
To install a single string of 155 Ah batteries
Note:
If you plan to install a second battery string in the riser compartment, go to the next procedure. If you do not plan to
install a second battery string, locate the Anderson connector for the second battery string and disconnect if required.