Dimensions
Base cabinet with Battery Compartment: 54”H x 24”W x 35”D
Base Cabinet with 2nd Battery Compartment Option: 66”H x 24”W x 35”D
Weight
Cabinet with Battery Compartment: 250 lbs. Equipped with one 155 Ah battery string: 650 lbs.
Mounting Options
Pre-Cast or Pour-in-Place Pad Template, FUTURE: Wall/H-Frame Mount and Vault/Riser (3rd
Party
Supplied)
AC Power Center Options
AC Power feed: 240 VAC single phase, 50/60HZ, 125 Amp service with UL listed service panel.
High power AC surge protection (Joslyn)
AC/DC Rectifier Option
Eltek Flatpack S (FPS) 1RU -48vdc Rectifier System No-LVD, Two 20 Amp rectifier modules,
autosenses and adjusts for low and high AC input
Smartpack S Controller.
Nominal Input Voltage Range: (185 - 270 VAC): Max. total power output 1000 Watts; Max. total
current
40 Amps (2 modules) or 20 Amps (2 modules N+1)
Battery Capacity
Designed to accommodate (2) strings of Northstar NSB 155FT RED batteries. One string support
in the standard battery compartment. Dual battery string support using expanded backup option
with second battery compartment orders. (Increases capacity to 310Ah total backup).
For all other battery types required, compartment space is as follows: 11.2”H x 5”W x 22”D
Cooling/Environmental
1000-Watt cooling capacity with Dantherm door mount heat exchanger
Ambient operating temperature range: -40°C to +46°C (-40°F to +115°F)
Wired Fiber Capacity
Up to 576 SC connector fiber terminations
Up to eighteen integrated PON splitters
Fiber Management Options
Fiber management: Up to 576 position fiber distribution in 144 or 288-port increments, SC/APC
connector, loose tube or ribbon. Up to eighteen integrated splitters in various ratios available
Available Rack Units
20RU in a standard 19” rack
6RU with full 576 fiber distribution SC ports and rectifier option
Safety and Compliance
Designed to Telcordia, GR-487, Generic Requirements for Electronic Equipment Cabinets, UL
E-6294
Specifications
Specifications for the Clearfield FiberFlex 2000 cabinet follow: