Sect06_CSMG_b.fm
6-4
04/22/2019
Steam Master Instruction Manual
6.5.3.1 Steam temperature reading with steam
generator in operation
a. Connect the test meter to the primary el-
ement of the dual element thermocouple
sensor.
b. Record the steam temperature. Remove
the meter leads from the primary element
when temperature is recorded.
c. Connect the test meter to the secondary
element of the dual element thermocou-
ple sensor.
d. Record the steam temperature. Remove
the meter leads from the secondary ele-
ment when done.
e. Record the steam temperature reading
from the separator thermometer.
f.
Compare the recorded temperatures with
the reference temperatures in Table 2-1
(Pressure-Temperature Table) in
Section 2. Make a note of the differences
for evaluation in paragraph 6.5.3.3.
6.5.3.2 Steam temperature reading with steam
generator in wet lay-up
NOTE
The machine should be in wet lay-up
for at least two hours following a
burner shut down. The cool-down
time may be reduced by increasing
the FILL rate.
a. Connect the test meter to the primary el-
ement of the dual element thermocouple
sensor.
b. Record the steam temperature. Remove
the meter leads from the primary element
when temperature is recorded.
c. Connect the test meter to the secondary
element of the dual element thermocou-
ple sensor.
d. Record the steam temperature. Remove
the meter leads from the secondary ele-
ment when done.
e. Record the feedwater temperature read-
ing on the thermometer on or near the
feedwater pump.
Alternatively, a feedwater temperature
reading from the thermometer on the hot-
well tank may be used.
6.5.3.3 Evaluate recorded values
a. The results from steps 6.5.3.1b and
6.5.3.1d should fall within 40 degrees of
the recorded steam temperature or the
value obtained from Table 2-1 Pressure/
Temperature Table (in Section 2).
b. The results from steps 6.5.3.2b and
6.5.3.2c should fall within 10 degrees of
the recorded incoming feedwater tem-
perature taken in step 6.5.3.2e.
c. If one of the coil temperature readings,
from either the primary element or the
secondary element, exceed the accepted
temperature range, then the correspond-
ing element wiring or connections are
faulty.
d. If both coil temperature readings, from
either the primary element or the second-
ary element, exceed the accepted tem-
perature range, and they are equal in the
error value, then it is likely that the ther-
mocouple elements are not making suffi-
cient contact with the sleeve that is
inserted in the tube. (See Fig. 2-2 in Sec-
tion 2.)
6.5.4
Check Main Temperature Limit
Controllers (MTLC)
a. Remove on thermocouple lead wire from
the MTLC.
b. Verify that a shutdown occurs and an
alarm is initiated within one minute.
c. Replace the thermocouple lead wire.
d. Repeat steps a, b, and c for other MTLC.
Summary of Contents for Steam Master CSMG-15
Page 1: ...STEAM MASTER SERIES USER MANUAL Cover CSMG 15 30 40 R027880B 20190603 ...
Page 8: ...vi The controls and features may differ depending on the unit s size and specifications ...
Page 9: ...vii The controls and features may differ depending on the unit s size and specifications ...
Page 14: ...Specifications_CSM_a fm xii 11 22 2018 This page intentionally left blank ...
Page 44: ...Sect05_CSMG_a fm 5 6 11 26 2018 Steam Master Instruction Manual NOTES ...
Page 68: ...HeatingSect_SM15_a fm A 2 04 30 2019 Fig 01A Main Heating Section SM15 ...
Page 69: ...04 30 2019 A 3 HeatingSect_SM15_a fm FIG 01A Main Heating Section SM15 ...
Page 70: ...HeatingSect_SM15_a fm A 4 04 30 2019 Fig 01B Economizer Stack Outlet Kit SM15 ...
Page 71: ...04 30 2019 A 5 HeatingSect_SM15_a fm FIG 01B Economizer Stack Outlet Kit SM15 ...
Page 72: ...HeatingSect_SM30_b fm A 6 12 05 2018 Fig 01C Main Heating Section SM30 ...
Page 73: ...12 05 2018 A 7 HeatingSect_SM30_b fm FIG 01C Main Heating Section SM30 ...
Page 74: ...HeatingSect_SM30_b fm A 8 12 05 2018 Fig 01D Economizer Coil SM30 ...
Page 75: ...12 05 2018 A 9 HeatingSect_SM30_b fm FIG 01D Economizer Coil SM30 ...
Page 76: ...HeatingSect_SM45_b fm A 10 04 30 2019 Fig 01C Main Heating Section SM40 ...
Page 77: ...04 30 2019 A 11 HeatingSect_SM45_b fm FIG 01C Main Heating Section SM40 ...
Page 78: ...HeatingSect_SM45_b fm A 12 04 30 2019 Fig 01D Economizer Coil SM40 Sht 1 of 2 ...
Page 79: ...04 30 2019 A 13 HeatingSect_SM45_b fm FIG 01D Economizer Coil SM40 ...
Page 86: ...Sep Trap PressMfld_SM153040_b fm A 20 04 30 2019 Fig 02E Pressure Indicating System ...
Page 87: ...04 30 2019 A 21 Sep Trap PressMfld_SM153040_b fm FIG 02E Pressure Indicating System ...
Page 90: ...PumpHkup C1 C2_parts_a fm A 24 03 05 2019 Fig 05A Pump Assy C1 ...
Page 91: ...03 05 2019 A 25 PumpHkup C1 C2_parts_a fm FIG 05A Pump Assy C1 ...
Page 92: ...03 05 2019 A 26 PumpHkup C1 C2_parts_a fm Fig 05B Pump Assy C2 ...
Page 93: ...PumpHkup C1 C2_parts_a fm A 27 03 05 2019 FIG 05B Pump Assy C2 ...
Page 98: ...Blank_Left fm A 32 08 16 2017 This page intentionally left blank ...
Page 106: ...R027906A 2018 10 22 ...
Page 107: ...NOTES ...
Page 108: ...Steam Generator Instruction Manual This page intentionally left blank ...
Page 109: ......