8. Failure description
If the unit detects a failure in the electronics it will display a failure code. The following table shows the
failure codes and the action required to solve the problem.
In case the unit displays a failure code that is not listed in the table, the unit needs service.
Table 5
Inv = Inverter, Chg = Charger
Failure
codes
Failure description
Failure
level
Affected
module
Solution
E001,E002 EEPROM memory failure.
Critical
All
Contact your retailer for service.
E003
Internal High Voltage
communication.
Critical
Inv/Chg
Contact your retailer for service.
E004
The internal electronics is getting too
cold.
Warning
Inv/Chg
Allow the unit to warm up, or place it in
a higher ambient temperature.
E005
The internal electronics is too cold.
Simple
Inv/Chg
Place the unit in higher ambient
temperature.
E006
The internal electronics is getting too
warm.
Warning
Inv/Chg
Allow the unit to cool down, or place it
in lower ambient temperature.
E007
The internal electronics is too warm.
Simple
Inv/Chg
Allow the unit to cool down, or place it
in lower ambient temperature.
E008,E009 A temperature sensor is broken.
Critical
All
Contact your retailer for service.
E010
The calculated efficiency of the unit
is too low.
Critical
All
Contact your retailer for service.
E020,E21
Inverter failure
Simple
Inv
Restart to remove failure. If a restart
does not remove the failure, contact
your retailer for service.
E022
Charger failure
Simple
Chg
Restart to remove failure. If a restart
does not remove the failure, contact
your retailer for service.
E030-‐E040 Missing calibration
Critical
All
Contact your retailer for service.
E049
DC Communication failure
Critical
DC in/out
Contact your retailer for service.
E050
Cell Voltage measurement failure
Critical
All
Contact your retailer for service.
E051
Battery Empty
Warning
Inv/DC out Apply charge current from 230VAC in or
12VDC in.
E052
One or more cell voltage(s) is getting
too low
Warning
All
Recharge the battery.
E053
One or more cell voltage(s) is too low Warning
All
Recharge the battery.
E054
One or more cell voltage(s) is getting
too high
Warning
All
Remove any charge inputs and allow the
unit to balance the cells.
Contact your retailer if the warning is
still present after 24hrs.
E055
One or more cell voltage(s) is too
high
Warning
All
Remove any charge inputs and allow the
unit to balance the cells.
Contact your retailer if the warning is
still present after 24hrs.
E056
One or more cell temperature(s) is
getting too low
Warning
All
Place the unit in higher ambient
temperature.
E057
One or more cell temperature(s) is
too low
Simple
All
Place the unit in higher ambient
temperature.
E058
One or more cell temperature(s) is Warning
All
Allow the unit to cool down or place it in