16/EN
DANGER:
Before starting any work on the electrical
installation, disconnect the product from the
mains supply.
There is the risk of electric shock!
Plug the power cable into the socket.
Gas connection
DANGER:
Product can be connected to gas supply
system only by an authorised and qualified
person or technician with licence.
Risk of explosion or toxication due to
unprofessional repairs!
Manufacturer shall not be held responsible for
damages arising from procedures carried out
by unauthorised or unlicensed persons.
DANGER:
Before starting any work on the gas
installation, disconnect the gas supply.
There is the risk of explosion!
•
Gas adjustment conditions and values are stated
on labels (or ion type label).
•
This product is suitable for connection with an
AGA approved hose assembly.
Suitable for Flexible Hose Connection
Suitable for Flexible Hose Connection
Suitable for Flexible Hose Connection
Suitable for Flexible Hose Connection
Connection hose must comply to AS1869 class
AS1869 class
AS1869 class
AS1869 class
B
B
B
B 10mm diameter & be AGA
AGA
AGA
AGA certified lenght of
hose is to be as short as possible hose lenght
must not exceed 1.2m the hose must not be
kinked or be able to touch any hot surface when
installed.
Gas connection for Natural Gas- 1.0 kPa
Your product is equipped for natural gas (NG).
Appliance should be connected using an isolation
valve, union and regulator.
1
Test point
2
Gas regulator
3
Elbow
4
Gas inlet pipe
Gas connection for LPG
Gas connection for LPG
Gas connection for LPG
Gas connection for LPG---- Propane Gas
Propane Gas
Propane Gas
Propane Gas---- 2.75 kPa
2.75 kPa
2.75 kPa
2.75 kPa
Appliance should be connected using an isolation
valve and union(regulator not required).
1
Test point
2
Test point adaptor
3
Elbow
4
Gas inlet pipe
Connecting with hose assembly
Where a hose assembly is to be used for the gas
connection to this appliance it must :
•
Comply to AS1869 Class B 10 mm diameter, be
AGA gas.
•
Be a short as possible, but in no case belonger
than 1.2 m.
•
This appliance is suitable for installation with a
hose assembly.
•
The hose must not be able to tuch any hot
surface of be kinked when appliance is installed.
•
At the completion of the installation, test for
leaks.
Do not use Naked Flame to test for leaks.
To ensure correct operation of the appliance it is
necessary to set the correct pressure for the appliance
1.0kPa for Natural Gas
1.0kPa for Natural Gas
1.0kPa for Natural Gas
1.0kPa for Natural Gas and 2.75 kPa for LPG
2.75 kPa for LPG
2.75 kPa for LPG
2.75 kPa for LPG
(Propane)
(Propane)
(Propane)
(Propane).
Check the pressure by connecting the pressure gauge
or manometer to test point as shown on adjacent
figures. Set pressure with 2-3 burners operating on
high.
Check for correct operation of burners, ignition system
etc and demonstrate operation of appliance to
customer.
If burner low setting requires adjustment refer to
conversion procedure for adjustment.