T H E C O N T I N U O U S P O W E R C O M P A N Y
Page 38
From the “Options” menu, click on the “Set value” tab for 5> Opt_Misc.
1) a. The “Sets CONTINUOUS (online) Operating Mode” is to set the UPS into Continuous
operation.
b. The “Sets STANDBY Operating Mode” is to set the UPS into Standby operation.
From the “Options” menu, click on the “Set Value” tab for 7> Backup Delay.
The Backup Delay allows you to set the time period of the utility AC noise rejection window.
Utility disturbances of duration less than this setting are ignored. Units are in 10msec.
This should be
“UPS
Output Unsynched to
Utility”.